ProSoft Technology MVI56E-MNET/MNETXT User Manual
Page 49

MVI56E-MNET / MNETXT ♦ ControlLogix Platform
Configuring the MVI56E-MNET Module
Modbus TCP/IP Interface Module
User Manual
ProSoft Technology, Inc.
Page 49 of 181
April 23, 2014
The first part of the record is the module information, which relates to the MVI56E
module, and the second part contains information required to interface to the
server device.
Command list example:
Enable
N
O
(0), Y
ES
(1), or C
ONDITIONAL
(2)
This field defines whether the command is to be executed and under what
conditions.
Value
Description
N
O
(0)
The command is disabled and will not be executed in the normal polling
sequence.
Y
ES
(1)
The command is executed each scan of the command list if the Poll Interval
time is set to zero. If the Poll Interval time is set to a nonzero value, the
command will be executed when the interval timer expires.
C
ONDITIONAL
(2) The command will execute only if the internal data associated with the
command changes. This value is valid only for write commands.