ProSoft Technology MVI56E-MNET/MNETXT User Manual

Page 56

background image

Configuring the MVI56E-MNET Module

MVI56E-MNET / MNETXT ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Interface Module

Page 56 of 181

ProSoft Technology, Inc.

April 23, 2014

Holding Register Offset

0 to 4999

This parameter defines the start register for the Modbus Command data in the
internal database. This parameter is enabled when a value greater than 0 is set.
For example, if the Holding Register Offset value is set to 4000, data requests for
Modbus Word register 40001 will use the internal database register 4000.
Function codes affected are 3, 6, 16, & 23.

Word Input Offset

0 to 4999

This parameter defines the start register for Modbus Command data in the
internal database. This parameter is enabled when a value greater than 0 is set.
For example, if the Word Input Offset value is set to 4000, data requests for
Modbus Word register address 30001 will use the internal database register
4000. Function code 4 is affected.

Connection Timeout

0 to 1200 seconds

This is the number of seconds the server will wait to receive new data. If the
server does not receive any new data during this time, it will close the
connection.