Modbus TCP/IP Client (Master)
Actively reads data from and writes data to Modbus TCP/IP devices, using
MBAP or Encapsulated Modbus message formats
Transmit Modbus Function Codes 1, 2, 3, 4, 5, 6, 7, 15, and 16
Offers one Client connection with up to 100 commands to talk to multiple
servers
ControlLogix processor can be programmed to use special functions to
control the activity on the Client by actively selecting commands to execute
from the command list (Command Control) or by issuing commands directly
from the ladder logic (Event Commands)
Status Data
Error codes, counters, and module status available from module memory
through the server, through the Client, or through the ladder logic and
controller tags in RSLogix™ 5000
5.1.3 Hardware Specifications
Specification
Description
Backplane Current Load
800 mA @ 5 Vdc
3 mA @ 24 Vdc
Operating Temperature
0°C to 60°C (32°F to 140°F)
Storage Temperature
-40°C to 85°C (-40°F to 185°F)
Shock
30 g operational
50 g non-operational
Vibration: 5 g from 10 Hz to 150 Hz
Relative Humidity
5% to 95% (without condensation)
LED Indicators
Battery Status (ERR)
Application Status (APP)
Module Status (OK)
4-Character, Scrolling, Alpha-
Numeric LED Display
Shows Module, Version, IP, Application Port
Setting, Port Status, and Error Information
Debug/Configuration/Application Ethernet port (E1)
Ethernet Port
10/100 Base-T, RJ45 Connector, for CAT5 cable
Link and Activity LED indicators
Auto-crossover cable detection
Shipped with Unit