beautypg.com

ProSoft Technology MVI56E-MNET/MNETXT User Manual

Page 109

background image

MVI56E-MNET / MNETXT ♦ ControlLogix Platform

Reference

Modbus TCP/IP Interface Module

User Manual

ProSoft Technology, Inc.

Page 109 of 181

April 23, 2014

Modbus TCP/IP Client (Master)
 Actively reads data from and writes data to Modbus TCP/IP devices, using

MBAP or Encapsulated Modbus message formats

 Transmit Modbus Function Codes 1, 2, 3, 4, 5, 6, 7, 15, and 16
 Offers one Client connection with up to 100 commands to talk to multiple

servers

 ControlLogix processor can be programmed to use special functions to

control the activity on the Client by actively selecting commands to execute
from the command list (Command Control) or by issuing commands directly
from the ladder logic (Event Commands)

Status Data
 Error codes, counters, and module status available from module memory

through the server, through the Client, or through the ladder logic and
controller tags in RSLogix™ 5000


5.1.3 Hardware Specifications

Specification

Description

Backplane Current Load

800 mA @ 5 Vdc
3 mA @ 24 Vdc

Operating Temperature

0°C to 60°C (32°F to 140°F)

Storage Temperature

-40°C to 85°C (-40°F to 185°F)

Shock

30 g operational
50 g non-operational
Vibration: 5 g from 10 Hz to 150 Hz

Relative Humidity

5% to 95% (without condensation)

LED Indicators

Battery Status (ERR)
Application Status (APP)
Module Status (OK)

4-Character, Scrolling, Alpha-
Numeric LED Display

Shows Module, Version, IP, Application Port
Setting, Port Status, and Error Information

Debug/Configuration/Application Ethernet port (E1)

Ethernet Port

10/100 Base-T, RJ45 Connector, for CAT5 cable
Link and Activity LED indicators
Auto-crossover cable detection

Shipped with Unit

5-foot Ethernet straight-through cable