Reference

MVI56E-MNET / MNETXT ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Interface Module

Page 116 of 181

ProSoft Technology, Inc.

April 23, 2014

Write Block

These blocks of data transfer information from the ControlLogix processor to the
module.

The following table describes the structure of the output image.

Write Block from Processor to Module

Word Offset

Description

Length

0

Write Block ID

1

1 to 200

Write Data

200

201 to 247

Spare

46

247

Select Priority Read Block

1

The Write Block ID is an index value used to determine the location in the
module’s database where the data will be placed. Each transfer can move up to
200 words (block offsets 1 to 200) of data.