beautypg.com

ProSoft Technology MVI56E-MNET/MNETXT User Manual

Page 42

background image

Configuring the MVI56E-MNET Module

MVI56E-MNET / MNETXT ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Interface Module

Page 42 of 181

ProSoft Technology, Inc.

April 23, 2014

2.2.4 Module

This section of the configuration describes the database setup and module-level
parameters.

Backplane Error/Status Pointer

1 to 4955

This parameter sets the address in the internal database where the backplane
error/status data will be placed. If you want the error/status data to be moved to
the processor and placed into the ReadData array, the value entered should be a
module memory address in the Read Data area. If the value is set to -1, the
error/status data will not be stored in the module's internal database and will not
be transferred to the processor's ReadData array.

Enabling the Error/Status Pointer is optional. The error/status data is routinely
returned as part of the input image, which is continually being transferred from
the module to the processor. For more information, see Normal Data Transfer
Blocks (page 113).

Read Register Start

0 to 4999

The Read Register Start parameter specifies the start of the Read Data area in
module memory. Data in this area will be transferred from the module to the
processor.

Note: Total user database memory space is limited to the first 5000 registers of module memory,

addresses 0 through 4999. Therefore, the practical limit for this parameter is 4999 minus the value

entered for Read Register Count, so that the Read Data Area does not try to extend above address

4999. Read Data and Write Data Areas must be configured to occupy separate address ranges in
module memory and should not be allowed to overlap.

Read Register Count

0 to 5000

The Read Register Count parameter specifies the size of the Read Data area of
module memory and the number of registers to transfer from this area to the
processor, up to a maximum of 5000 words.

Note: Total Read Register Count and Write Register Count cannot exceed 5000 total registers.

Read Data and Write Data Areas must be configured to occupy separate address ranges in
module memory and should not be allowed to overlap.