ProSoft Technology MVI56E-MNET/MNETXT User Manual

Page 21

background image

MVI56E-MNET / MNETXT ♦ ControlLogix Platform

Start Here

Modbus TCP/IP Interface Module

User Manual

ProSoft Technology, Inc.

Page 21 of 181

April 23, 2014

Important: You must select the C

OMM

F

ORMAT

as D

ATA

-

INT in the dialog box, otherwise the

module will not communicate over the backplane of the ControlLogix rack.

4 Click OK

to continue.

5 Edit the Module Properties. Select the R

EQUESTED

P

ACKET

I

NTERVAL

value

for scanning the I/O on the module. This value represents the minimum
frequency at which the module will handle scheduled events. This value
should not be set to less than 1 millisecond. The default value is 5
milliseconds. Values between 1 and 10 milliseconds should work with most
applications.

6 Save the module.

Click OK

to close the dialog box. Notice that the module now appears in the

Controller Organization window.