1.7.1 Creating the Module
1 Add the MVI56E-MNET module to the project.
In the Controller Organization window, select I/O
C
ONFIGURATION
and click
the right mouse button to open a shortcut menu. On the shortcut menu,
choose N
EW
M
ODULE
...
This action opens the Select Module
dialog box.
2 Select the 1756-M
ODULE
(G
ENERIC
1756
M
ODULE
)
from the list and click OK.
This action opens the New Module dialog box.
3 In the New Module dialog box, enter the following values.
Parameter
Value
Name
Enter a module identification string. Example: MNET.
Description
Enter a description for the module. Example: M
ODBUS
TCP/IP
I
NTERFACE
M
ODULE
Comm Format
Select D
ATA
-INT.
Slot
Enter the slot number in the rack where the MVI56E-MNET
module is located.
Input Assembly Instance
1
Input Size
250
Output Assembly Instance
2
Output Size
248
Configuration Assembly Instance
4
Configuration Size
0