MVI56E-MNET / MNETXT ♦ ControlLogix Platform

Reference

Modbus TCP/IP Interface Module

User Manual

ProSoft Technology, Inc.

Page 161 of 181

April 23, 2014

Parameter

Value

Name

Enter a module identification string. Example: MNET_2

Description

Enter a description for the module. Example: M

ODBUS

TCP/IP

I

NTERFACE

M

ODULE

Comm Format

Select D

ATA

-INT.

Slot

Enter the slot number in the rack where the MVI56E-
MNET module is located.

Input Assembly Instance

1

Input Size

250

Output Assembly Instance

2

Output Size

248

Configuration Assembly Instance

4

Configuration Size

0

4 Select the Requested Packet Interval value for scanning the I/O on the

module. This value represents the minimum frequency that the module will
handle scheduled events. This value should not be set to less than 1
millisecond. The default value is 5 milliseconds. Values between 1 and 10
milliseconds should work with most applications.