MVI56E-MNET / MNETXT ♦ ControlLogix Platform

Reference

Modbus TCP/IP Interface Module

User Manual

ProSoft Technology, Inc.

Page 157 of 181

April 23, 2014

5.6.5 Writing the Ethernet Settings to the Module

Expand the MVI56EMNETEthernet

controller tag.

Set the new Ethernet configuration in MVI56EMNETEthernet.Config:

Move a value of 1 to MVI56MNETEthernet.Write.

After the message is executed, the MVI56MNETEthernet.Write

bit resets to 0.

To check the status of the message, refer to the WriteEthernetMSG tag.