beautypg.com

Retrotec DM-2 User Manual

Page 65

background image

Page 65 of 72
©Retrotec Inc. 2012

Appendix D: Adjust Flow values for temperature difference

Temperature correction is only required when there is a temperature difference between the area
under test, (inside), and the area used as reference for the test, (outside).

To use the tables, determine if you are pressurizing or pressurizing. When pressurizing, the air flow of
the fan will be toward the inside, and when depressurizing, the air flow will be toward the outside.

Choose the correction factor from Table 17 for the depressurize case or Table 18 for the pressurize
case based on the current inside and outside temperatures. Multiply the flow you measured by the
factor to get the air flow corrected for temperature difference.

Retrotec’s FanTestic software automatically corrects flow values for any temperature difference when
inside and outside temperatures are entered into the software.

Table 17: Temperature correction factors for enclosure DEPRESSURIZATION

50

55

60

65

70

75

80

85

90

-20

0.848

0.844

0.840

0.836

0.832

0.828

0.824

0.820

0.816

-15

0.857

0.853

0.849

0.845

0.841

0.837

0.833

0.829

0.826

-10

0.867

0.863

0.859

0.855

0.851

0.847

0.843

0.839

0.835

-5

0.877

0.872

0.868

0.864

0.860

0.856

0.852

0.848

0.844

0

0.886

0.882

0.878

0.874

0.869

0.865

0.861

0.857

0.854

5

0.896

0.892

0.887

0.883

0.879

0.875

0.871

0.867

0.863

10

0.906

0.901

0.897

0.893

0.888

0.884

0.880

0.876

0.872

15

0.915

0.911

0.906

0.902

0.898

0.894

0.890

0.885

0.881

20

0.925

0.920

0.916

0.912

0.907

0.903

0.899

0.895

0.891

25

0.935

0.930

0.926

0.921

0.917

0.912

0.908

0.904

0.900

30

0.944

0.940

0.935

0.931

0.926

0.922

0.918

0.913

0.909

35

0.954

0.949

0.945

0.940

0.936

0.931

0.927

0.923

0.919

40

0.964

0.959

0.954

0.950

0.945

0.941

0.936

0.932

0.928

45

0.973

0.968

0.964

0.959

0.955

0.950

0.946

0.941

0.937

50

0.983

0.978

0.973

0.969

0.964

0.960

0.955

0.951

0.946

55

0.992

0.988

0.983

0.978

0.974

0.969

0.964

0.960

0.956

60

1.002

0.997

0.992

0.988

0.983

0.978

0.974

0.969

0.965

65

1.012

1.007

1.002

0.997

0.992

0.988

0.983

0.979

0.974

70

1.021

1.016

1.011

1.007

1.002

0.997

0.993

0.988

0.983

75

1.031

1.026

1.021

1.016

1.011

1.007

1.002

0.997

0.993

80

1.041

1.036

1.031

1.026

1.021

1.016

1.011

1.007

1.002

85

1.050

1.045

1.040

1.035

1.030

1.025

1.021

1.016

1.011

90

1.060

1.055

1.050

1.045

1.040

1.035

1.030

1.025

1.021

95

1.070

1.064

1.059

1.054

1.049

1.044

1.039

1.035

1.030

100

1.079

1.074

1.069

1.064

1.059

1.054

1.049

1.044

1.039

105

1.089

1.084

1.078

1.073

1.068

1.063

1.058

1.053

1.048

110

1.098

1.093

1.088

1.083

1.078

1.073

1.068

1.063

1.058

Inside Temperature (F)

O

ut

s

ide

Te

m

pe

ra

ture

(

F)