beautypg.com

A-1 inverter/charger specifi cations, Models – Magnum Energy ME Series User Manual

Page 59

background image

Page 51

©

2012 Magnum Energy, Inc.

Appendix A - Specifi cations and Optional Equipment

Appendix A - Specifi cations and Optional Equipment

A-1 Inverter/Charger

Specifi cations

Models

ME2000 (-15B, -20B) ME2012 (-15B, -20B)

ME2512

ME3112

Inverter Specifi cations

Input Battery Voltage Range

9 to 16 VDC

9 to 16 VDC

9 to 16 VDC

9 to 16 VDC

Absolute Maximum DC Input

25 VDC

25 VDC

25 VDC

25 VDC

AC Output Voltage Accuracy

120 VAC ±5% (≤ continuous power)

Output Frequency and Accuracy

60 Hz ± 0.1 Hz

Continuous Power Output (at 45°C)

2000 VA

2000 VA

2500 VA

3100 VA

Continuous AC Output Current

17 A

17 A

21A

26 A

1 msec Surge Current (amps AC)

60

60

100

120

100 msec Surge Current (amps AC)

37

37

45

50

5 sec Surge Power (real watts)

3700

3700

5000

6000

30 sec Surge Power (real watts)

3450

3450

4500

4800

5 min Surge Power (real watts)

3100

3100

3500

3950

30 min Surge Power (real watts)

2400

2400

2900

3500

Rated Input Battery Current

266 ADC

266 ADC

333 ADC

413 ADC

Inverter Effi ciency (peak)

95%

95%

91%

90%

HBCO/HBCI (High Battery Cut Out/In)

≥15.8 VDC

LBCO/LBCI (Low Battery Cut Out/In)

9.0 VDC (adj)/12.5 VDC

Series Stacking 120/240 VAC

No

Transfer Time

16 msecs

Search Mode (typical)

5 watts

No Load (120 VAC output, typical)

20 watts

20 watts

23 watts

25 watts

Waveform

Modifi ed Sine Wave

Charger Specifi cations

Continuous Output at 45°C

100 ADC

100 ADC

120 ADC

160 ADC

Input Current - Rated Output (AC amps)

15

15

18

22

Charger Effi ciency

85%

AC Input Frequency Range

50 to 70 Hz

AC Input Voltage Range

60 to 140 VAC (120 VAC nominal)

Power Factor

> 0.95

General Features and Capabilities

Transfer Relay Capability

Single leg in at 30 amps

Two input legs at 30 amps each, or combine for 60 amps*

Five-stage Charging Capability

Bulk, Absorb, Float, Equalize (requires remote), and Battery Saver™

Battery Temperature Compensation

Yes, 15 ft Battery Temp Sensor standard

Internal Cooling

0 to 120 cfm variable speed drive using dual 92 mm brushless DC fan

Overcurrent Protection

Yes, with two overlapping circuits

Over-temperature Protection

Yes, on transformer, MOSFETS, and battery

Corrosion Protection

PCB’s conformal coated, powder coated chassis/top, and stainless steel fasteners

Safety Listings

ETL listed to UL/cUL 458, and CSA C22.2 # 107.1-01

Warranty

3 years parts and labor

Dual Branch-Rated Output Breakers

Optional on ME2000 (15 or 20 amp breakers) or ME2012 (15 or 20 amp breakers)

Environmental Specifi cations

Operating Temperature

-20°C to +60°C (-4°F to 140°F)

Non-operating Temperature

-40°C to +70°C (-40°F to 158°F)

Operating Humidity

0 to 95% RH non-condensing

Physical Specifi cations

Unit Dimensions (h x w x d)

13.75” x 12.65” x 7.0”

(17.8 cm)

13.75” x 12.65” x 8.0” (34.9 cm x 32.1 cm x 20.3 cm)

Shipping Dimensions (h x w x d)

19” x 15” x 13” (48.3 cm x 38.1 cm x 33 cm)

Mounting

Shelf (top or bottom up) or wall (no uncovered vents on top or bottom)

Unit Weight

37 lb (16.8 kg)

37 lb (16.8 kg)

41 lb (18.6 kg)

46 lb (20.9 kg)

Shipping Weight

45 lb (20.4 kg)

46 lb (20.9 kg)

51 lb (23.1 kg)

56 lb (25.4 kg)

Max operating altitude

15,000’ (4570 m)

Specifi cations @ 25°C (unless otherwise noted) - Subject to change without notice.
* The pass-thru capability on each leg of the -15B and -20B models is limited by the output breaker size on each output.