Single in / dual out wiring, Direct from inverter (inverter loads) – Magnum Energy ME Series User Manual
Page 35
Page 27
©
2012 Magnum Energy, Inc.
Installation
Main Panel
(Utility Power/Generator Input)
ME2012-15B or
ME2012-20B Inverter
AC Terminal Block
(AC input and output wiring)
SINGLE IN / DUAL OUT wiring
AC HOT 1
IN
(from Mai
n
Panel)
AC HOT 1 OUT
AC NEUT
IN
(from Mai
n
Panel)
AC NEUT OUT
(x
2)
AC HOT 2 OUT
Direct from inverter
(Inverter Loads)
120
VAC
120
VAC
AC GROUNDS
(to/from
both panels)
ON
OFF
ON
OF
F
ON
OF
F
ON
OF
F
ON
OFF
ON
OF
F
ON
OF
F
ON
OF
F
ON
OF
F
ON
OF
F
ON
OF
F
ON
OF
F
ON
OF
F
30
Maximum breaker size required
to inverter AC input
depends on model used.
ME2012-15B: 45-amp breaker
(single pole);
ME2012-20B: 60-amp
breaker (single pole). These
breaker sizes allow full charging
and full pass-thru capability for
your inverter model.
In mobile installations: neutral is typically not
connected to ground in the main panel.
AC HOT 2
IN
(from Mai
n
Panel)
Has optional 15-amp or 20-
amp branch-rated circuit
breakers (on side of unit).
Figure 2-11, AC Wiring for Single In - Dual Out Confi gurations