beautypg.com

4 wiring the dc overcurrent protection device, 5 wiring the battery bank – Magnum Energy ME Series User Manual

Page 26

background image

©

2012 Magnum Energy, Inc

Page 18

Installation

2.4.4

Wiring the DC Overcurrent Protection Device

A fuse/disconnect or circuit breaker must be provided in the DC positive line between the battery

and the inverter to protect the DC wiring system. Mount the fuse block (or circuit breaker assembly)

as near as practical to the batteries. For maximum protection, install it within 18 inches (45 cm)

of the battery.
1. Open the fuse disconnect (or open the circuit breaker) and connect a short cable (same rating

as the battery cables) to one end of the fuse block.

2. Connect the short cable to the positive battery terminal.
3. Connect the positive cable (RED) from the inverter to the fuse/disconnect (or circuit breaker)

assembly. DO NOT connect the positive cable to the inverter at this time.

4. Securely tighten the fuse/disconnect (or circuit breaker) connection lugs. Once the entire

installation is complete and all connections are verifi ed, close the fuse disconnect (or circuit
breaker) to provide power to the inverter.

2.4.5

Wiring the Battery Bank

WARNING: Lethal currents will be present if the positive and negative cables attached

to the battery bank touch each other. During the installation and wiring process, ensure

the cable ends are insulated or covered to prevent touching/shorting the cables.
Info: DO NOT connect the DC wires from the battery bank to the inverter until: 1) all

DC and AC wiring are completed, 2) the correct DC and AC overcurrent protection have

been installed, and 3) the correct DC voltage and polarity have been verifi ed.
Info: For the ME Series inverter/charger to perform optimally, a minimum battery bank

of 200 AH is recommended for moderate loads (<1000W) and greater than 400 AH for

heavy loads (≥1000W).

Depending upon the voltage of the batteries you use in the installation (6 or 12 VDC), the batteries

must be wired in series, parallel, or series-parallel to provide the correct voltage (see Appendix B –

Battery Information for guidance on wiring batteries together). The interconnecting DC wires must be

sized and rated exactly the same as those that are used between the battery bank and the inverter.
Place the batteries as close as practical to the inverter, preferably in an insulated and ventilated

enclosure. Allow adequate space above the batteries to access the terminals and vent caps (as

applicable). Also, allow at least 1” (2.5 cm) of space between the batteries to provide good air

fl ow. DO NOT mount the batteries directly under the inverter.

CAUTION: Install batteries in a well ventilated area. Batteries can produce explosive

gases. For compartment/enclosure installations, always vent batteries to the outside.

Info: To ensure the best performance from your inverter system, batteries should be of

the same size, type, rating, and age. Do not use old or untested batteries.