Installation

2.1.3 Locating the Inverter

Only install the inverter in a location that meets the following requirements:
Clean and Dry – The inverter should not be installed in an area that allows dust, fumes, insects, or

rodents to enter or block the inverter’s ventilation openings. This area also must be free from any

risk of condensation, water, or any other liquid that can enter or fall on the inverter. The inverter

uses stainless steel fasteners, plated copper busbars, and a power-coated aluminum base. The

internal circuit boards are conformal coated. All of this is done to help fi ght the harmful effects

of corrosive environments. However, the inverter’s life is uncertain if used in the above types of

environments, and inverter failure under these conditions is not covered under warranty.

Info: If the inverter is installed in an area where moisture may occur, we recommend

putting silicone dielectric grease compound into the electrical ports (Items 3-6 as

shown in Figure 1-1). Before installing the cables, or if leaving any ports open, squirt a

liberal amount into each port. Silicone dielectric compound makes an

effective moisture

and corrosive barrier to help protect and prevent corrosion to the RJ11 connections.

Cool – The inverter should be protected from direct sun exposure or equipment that produces

extreme heat. The ambient temperature around the inverter must not exceed 77°F (25°C) to

meet power specifi cations.
Ventilation – In order for the inverter to provide full output power and avoid over-temperature

fault conditions; do not cover or block the inverter’s ventilation openings, or install this inverter in

an area with limited airfl ow. The inverter uses two fans to provide forced-air cooling, these fans

pull in air through the intake vents (see Figure 1-2, Item 9) and blow out air through the exhaust

vents (see Figure 1-3, Item 13). Allow at the minimum an airspace clearance of 6” (15.2 cm) at

the intake and exhaust vents, and 3” (7.6 cm) everywhere else to provide adequate ventilation.
If installed in an enclosure, a fresh-air intake opening must be provided directly to the front side

(intake vents) of the inverter, and an exhaust opening on the back side (exhaust vents) of the

inverter. This allows cool air from the outside to fl ow into the inverter, and heated air to exit the

inverter and the enclosure. When mounted in an enclosed compartment, airfl ow must be ≥ 100

cfm in order to maintain no more than a 68°F (20°C) rise in compartment temperature.

CAUTION: Do not mount this inverter in a zero clearance compartment, nor cover or

obstruct the ventilation openings—overheating may result.

Safe – Keep any fl ammable/combustible material (e.g., paper, cloth, plastic, etc.) that may be

ignited by heat, sparks, or fl ames at a minimum distance of 2 feet (61 cm) away from the inverter.

WARNING: The ME Series inverter/charger is not ignition-protected. Do not install this

inverter in any area that contains extremely fl ammable liquids like gasoline or propane.

Close to the battery bank – The inverter should be located as close to the batteries as possible.

Long DC wires tend to loose effi ciency and reduce the overall performance of an inverter. However,

the unit should NOT be installed in the same compartment as the batteries, or mounted where it

will be exposed to gases produced by the batteries. These gases are corrosive and will damage the

inverter; also, if these gases are not ventilated and allowed to collect, they could ignite and cause

an explosion.
Accessible Do not block access to the inverter’s remote control and accessory ports, as well

as the inverter’s controls and status indicator. Also allow enough room to access the AC and DC

wiring terminals and connections, as they will need to be checked and tightened periodically. See

Figure 2-3 for the ME Series’ inverter/charger dimensions.
Away from sensitive electronic equipment – High-powered inverters can generate levels

of RFI (Radio Frequency Interference). Locate any electronic equipment susceptible to radio

frequency and electromagnetic interference as far away from the inverter as possible.