Shutdown/Disassembly
Page 28
Operating Instructions Powador Argus 16S DCS, 24S DCS_EN
Authorised electrician
10
Shutdown/Disassembly
10.1 Shutting down the string monitoring box
DANGER
Lethal voltages are still present in the terminals and leads in the string monitoring box even
after the string monitoring box has been switched off and disconnected.
Touching the leads and terminals in the string monitoring box can result in severe injury or death.
When there is irradiance, DC voltage is present on the exposed ends of the DC leads. Arcing may
occur if the DC leads are disconnected while under a load.
›
It is absolutely necessary that the shutdown sequence be carried out in the correct order.
›
When working on photovoltaic modules, in addition to disconnecting from the grid, always
disconnect the DC main switch on the generator junction box (or the DC plug connectors).
It is not sufficient just to disconnect the mains.
Shutdown sequence
1. Switch off the mains by turning off the external circuit breakers.
2. Disconnect the PV generator using the DC disconnect.
DANGER! The DC leads remain live.
"
Ensure that there is no voltage present on the grid connection terminals.
10.2 Decommissioning the string monitoring box
↻ Turn off the string monitoring box.
1. Open the connection area.
2. Remove the interface cable.
3. Detach DC connection plug.
4. Open the cable fittings.
5. Pull out the leads.
»
The string monitoring box is decommissioned. Continue by unmounting the unit.
10.3 Unmounting the string monitoring box
↻ Turn off the string monitoring box.
↻ Decommission the string monitoring box.
1. Unscrew the detachment protector.
2. Take the string monitoring box down from the mounting plate.
3. Pack the string monitoring box securely if it is to be used again,
or
dispose of the unit properly.