ARGUS ADDRESS

00

right button OK or CANCEL,

then right button

left button

(select item/entry)

right button

(change value)

ENTER ARGUS ADDRESS

00

OK

CANCEL

8.3.1 Display: “ENTER ARGUS ADDRESS”

You can set a unique RS485 address between 00 and 99 on this menu. With a bus system such as the RS485, each

unit sharing the bus must possess a unique address, regardless of whether it is an inverter or a current sensor.

8.3.2 Display: “ENTER DISPLAY LANGUAGE”

Here you can set the display language (currently only English).

8.3.3 Display: “ENTER COMMUNICATION PROTOCOL”

Here you can set the communication protocol to the data logger:

0 for XP series inverters

1 for Powador-proLOG

8.3.4 Display: “ENTER ANALOG CONFIGURATION”

Here you can set the number of connected analogue channels. Values between 0 and 4 are possible.

8.4 Technical settings display

You can do the following from this display:

Display all current channels

Change address of combiner box circuit boards

Perform calibration

8.4.1 Display: “Current current values (test mode)”

In this display, all current values of the strings are shown simultaneously.