Yaskawa DriveWizard AC Drive User Manual
Page 146

P5+
Par.
P5+ Parameter
Name
Conversion
E7/P7
Par.
E7/P7 Parameter
Name
n033
Motor Rated Current
None
E2-01
r Rated Current
Moto
n034
Motor OL Select
If n033 > 1, then L1-01 =
1
L1-01
Mtr OL Protect Select
n035
OH1 Stop Method
3
re-Alarm Op Sel.
None
L8-0
OH P
n036
Terminal S2 Select
If n036 >1, then table 4,
else H1-03 = 0Fh
H1-01
Terminal S3 Select
n037
Terminal S3 Select
Table 4
H1-02
Terminal S4 Select
n038
Terminal S4 Select
Table 4
H1-03
Terminal S5 Select
n039
Terminal S5 Select
Table 4
H1-04
Terminal S6 Select
n040
Terminal S6 Select
Table 4
H1-05
Terminal S7 Select
n041
Terminal MA Select
Table 5
H2-01
Terminal M1-M2 Sel.
n042
Terminal M1 Select
Table 5
H2-02
Terminal M3-M4 Sel.
n043
Analog Input Select
D
NA
NA
NOT CONVERTE
n044
Terminal FI Select
If n044 =1, then H3-08
=2, else H3-08 = 0
H3-08
Terminal A2 Signal Level
Select
n045
MOP Ref Memory
ONVERTED
NOT C
NA
NA
n046
Ref Loss Detect
5
Ref Loss Det Sel
None
L4-0
Freq
n047
Freq Lvl @ F Ref Loss
n047*10 = L4-06
L4-06
Freq Ref Lvl@loss
n048
Terminal FV Gain
n048*10 = H3-02
H3-02
Terminal A1 Gain
n049
Terminal FV Bias
n049*10 = H3-03
H3-03
Terminal A1 Bias
n050
Terminal FI Gain
n050*10 = H3-10
H3-10
Terminal A2 Gain
n051
Terminal FI Bias
n051*10 = H3-11
H3-11
Terminal A2 Bias
n052
Terminal AM Sel
Table 6
H4-01
Terminal FM Select
n053
Terminal AM Gain
n053*10 = H4-02
H4-02
Terminal FM Gain
n054
Carrier Freq select
ONVERTED
NA
NA
NOT C
n055
Pwr Loss Ride Thru sel
None
L2-01
t Select
Pwr Loss De
n056
t
Spd Srch Current
None
b3-02
Spd srch Deact Curren
n057
Min Baseblock Time
If n057 > 5.0 then L2-03 =
5.0, else n057 = L2-03
L2-03
Pwr Loss Min Base Block
Time
n058
rch V/F
NOT CONVERTED
NA
NA
Spd Sea
n059
Pwr Loss Ride Thru Time None
L2-02
Loss Ride-Thru Time
Pwr
n060
Number of Restarts
None
L5-01
f Restart attempts
No.o
n061
Restart Select
If n061 = 1 then L5-02 =
0, else L5-02 = 1
L5-02
Auto Restart Operation
Select
n062
Jump Freq 1
If n062 > 200.0, then d3-
01 = 200.0, else n062 =
d3-01
d3-01
Jump Frequency 1
n063
Jump Freq 2
If n063 > 200.0, then d3-
02 = 200.0, else n063 =
d3-02
d3-02
Jump Frequency 2
n064
Jump Bandwidth
If n064 > 20.0, then d3-04
= 20.0, else n064 = d3-04
d3-04
Jump Frequency Width
n065
Elapsed Timer Select
t
None
o2-08
Cum. Op Time Selec
n066
Elapsed Time 1
NOT CONVERTED
NA
NA
n067
Elapsed Time 2
NOT CONVERTED
NA
NA
n068
DC inj Current
None
b2-02
nj Brkg Current
DC I
n069
DC inj Time @ Stop
n069*10 = b2-04
b2-04
DC INJ Time @Stop
n070
DC inj Time @ Start
n070*10 = b2-03
b2-03
DC INJ Time @ Start
n071
NA
Torq Comp Gain
NOT CONVERTED
NA
n072
Stall Prev Sel. on Decel
Stall Prev Decel
None
L3-04
146