GPD 50
d GPD
P7 C
sion Tables
Table 1: Parameter conversion
6/P5+ to E7 an
506/P5+ to
onver
P5+
Par.
P5+ Parameter
Name
Conversion
E7/P7
Par.
E7/P7 Parameter
Name
n001
it
Param selection/ in
NOT CONVERTED
NA
NA
n002
Op Mode Select
See Table 2
b1-01 &
b1-02
Run Seq Select
Ref Select
n003
Motor Rated Voltage
n003/10 = E1-01
E1-01
Input Voltage
n004
Stop Method
If n004 > 1, then b1-03
=3, else n004 = b1-03
b1-03
Stopping Method
n005
Phase Rotation
n006
Reverse Prohibited
See Table 3
b1-04
Reverse operation
n007
Local/Remote
None
o2-01
l / Remote Key
Loca
n008
Stop Key Function
None
o2-02
n009
Freq Ref Setting from
Digital Operator
If n009=1, then o2-05=0,
else o2-05 = 1
o2-05
Freq Ref Setting Method
Selection
n010
V/F Pattern Select
ONVERTED
NA
NOT C
NA
n011
Max Frequency
If n011 > 120.0 then E1-
04 =120.0, else n011 =
E1-04
E1-04
Max Output Freq.
n012
Max voltage
None
E1-05
Max Output Voltage
n013
Base Frequency
If n013 > 200.0 then E1-
06 =200.0, else n013 =
E1-06
E1-06
Base Frequency
n014
Mid Frequency
If n014 > 200.0 then E1-
07 =200.0, else n014 =
E1-07
E1-07
Mid Frequency
n015
Mid voltage
None
E1-08
Mid Voltage A
n016
Min Frequency
None
E1-09
Min Frequency
n017
Min V
Min Voltage
None
E1-10
oltage
n018
Accel Time 1
If n018 > 999.9, then
n018*10 = C1-01, else
n018 = C1-01
C1-01
Acceleration Time 1
n019
Decel Time 1
If n019 > 999.9, then
n018*10 = C1-02, else
n019 = C1-02
C1-02
Deceleration Time 1
n020
Accel Time 2
n020 *10 = C1-03
C1-03
Acceleration Time 2
n021
Decel Time 2
n021*10 = C1-04
C1-04
Deceleration Time 2
n022
S-curve select
NOT CONVERTED
NA
NA
n023
Operator Display Units
If n023 >39 then n023*10
= o1-03, else n023 = o1-
03
o1-03
Digital Operator Display
Selection
n024
Freq Reference #1
n025*10 = d1-01
d1-01
Frequency Reference 1
n025
Freq Reference #2
n026*10 = d1-02
d1-02
Frequency Reference 2
n026
Freq Reference #3
n027*10 = d1-03
d1-03
Frequency Reference 3
n027
Freq Reference #4
n028*10 = d1-04
d1-04
Frequency Reference 4
n028
D
Freq Reference #5
NOT CONVERTE
NA
NA
n029
Freq Reference #6
NOT CONVERTED
NA
NA
n030
Jog Reference
n030*10 = d1-17
d1-17
Jog Freq. reference
n031
Freq Ref Upper Limit
n031*10 = d2-01
d2-01
Freq Ref. Upper Limit
n032
Freq Ref Lower Limit
n032*10 = d2-02
d2-02
Freq. Ref. Lower Limit
145