P5 to e7/p7 conversion tool table, Gpd5 conve ta table 1: parameter conversion – Yaskawa DriveWizard AC Drive User Manual
Page 140

G
PD5
Conve
Ta
Table 1: Parameter Conversion
PD
505/P5 to E7 and G
05/P5 to P7
rsion
bles
P5
Par.
P5 Parameter Name
Conversion
E7/P7
Par.
E7/P7 Parameter
Name
n001 Param selection/ init
NVERTED
NOT CO
NA
NA
n002
Op Mode Select
See Table 2
b1-01 &
b1-02
Run Seq Select
Ref Select
n003
Motor Rated Voltage
n003/10 = E1-01
E1-01
Input Voltage
n004
Stop Method
If n004 > 1, then b1-03 =3,
else n004 = b1-03
b1-03
Stopping Method
n005
Phase Rotation
n006
Reverse Prohibited
See Table 3
b1-04
Reverse operation
n007
Local/Remote
None
o2-01
Local / Remote Key
n008
Stop Key Function
o2-02
None
n009
Freq Ref Setting from
Digital Operator
If n009=1, then o2-05=0,
else o2-05 = 1
o2-05
Freq Ref Setting Method
Selection
n010
V/F Pattern Select
NOT CONVERTED
NA
NA
n011 Motor Rated Voltage
NOT CONVERTED
NA
NA
n012
Max Frequency
If n012 > 120.0 then E1-04
=120.0, else n012 = E1-04
E1-04
Max Output Freq.
n013
Max voltage
None
E1-05
Output Voltage
Max
n014
Base Frequency
If n014 > 200.0 then E1-06
=200.0, else n014 = E1-06
E1-06
Base Frequency
n015
Mid Frequency
If n015 > 200.0 then E1-07
=200.0, else n015 = E1-07
E1-07
Mid Frequency
n016
Mid voltage
None
E1-08
oltage A
Mid V
n017
Min Frequency
None
E1-09
Min Frequency
n018
Min Voltage
None
E1-10
ltage
Min Vo
n019
Accel Time 1
If n019 > 999.9, then
n019*10 = C1-01, else n019
= C1-01
C1-01
Acceleration Time 1
n020
Decel Time 1
If n020 > 999.9, then
n020*10 = C1-02, else n020
= C1-02
C1-02
Deceleration Time 1
n021
Accel Time 2
If n021 > 999.9, then n021
*10 = C1-03, else n021 =
C1-03
C1-03
Acceleration Time 2
n022
Decel Time 2
If n022 > 999.9, then
n022*10 = C1-04, n022 =
C1-04
C1-04
Deceleration Time 2
n023
S-curve select
NOT CONVERTED
NA
NA
n024
Operator Display Units
If n024 >39 then n024*10 =
o1-03, else n024 = o1-03
o1-03
Digital Operator Display
Selection
n025
Freq Reference #1
n025*10 = d1-01
d1-01
Frequency Reference 1
n026
Freq Reference #2
n026*10 = d1-02
d1-02
Frequency Reference 2
n027
Freq Reference #3
n027*10 = d1-03
d1-03
Frequency Reference 3
n028
Freq Reference #4
n028*10 = d1-04
d1-04
Frequency Reference 4
n029
Jog Reference
n029*10 = d1-17
d1-17
Jog Freq. reference
n030
Freq Ref Upper Limit
n030*10 = d2-01
d2-01
Freq Ref. Upper Limit
n031
Freq Ref Lower Limit
n031*10 = d2-02
d2-02
Freq. Ref. Lower Limit
n032
Motor Rated Current
None
E2-01
Motor Rated Current
140