11 appendix 3 terminal size and wire gauge – Yaskawa F7 to A1000 User Manual
Page 67

11 Appendix 3 Terminal Size and Wire Gauge
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
67
Table 21 Control Circuit Terminal Size and Wire Gauge
Power Supply
Series
Capacity
Terminal Signal
Terminal Screw
Tightening Torque
lb-in
(N ・ m)
Possible Gauges
AWG (mm
2
)
Recommended
Gauges AWG
(mm
2
)
200 V Class
400 V Class
F7
All capacities
FM, AC, AM, A1,
A2, A3, +V, -V,
S1, S2, S3, S4, S5,
S6,S7, S8, SN, SC,
SP, RP, MA, MB,
MC, M1,M2, M3,
M4, M5, M6,
Phoenix type
4.2 to 5.3
(0.5 to 0.6)
Stranded wire: 26 to
16
(0.14 to 1.5)
18
(0.75)
MP, RP, R+, R-, S+,
S-, IG
Phoenix type
4.2 to 5.3
(0.5 to 0.6)
Stranded wire:
26 to 16
(0.14 to 1.5)
18
(0.75)
E (G)
M3.5
7.0 to 8.8
(0.8 to 1.0)
20 to 14
(0.5 to 2.0)
12
(1.25)
200 V Class
400 V Class
A1000
All capacities
FM, AC, AM, P1,
P2, PC,
SC, SN, SP, A1, A2,
A3, +V, -V,
S1, S2, S3, S4, S5,
S6,S7, S8,
MA, MB, MC,
M1-M6
M3
4.4 to 5.3
(0.5 to 0.6)
stranded wire:
24 to 16
(0.2 to 1.0)
solid wire:
24 to 16
(0.2 to 1.5)
Ferrule-Type:
24 to 20 (0.25 to 0.5)
Bare Wire: 18 (0.75)
Ferrule-Type: 20 (0.5)
MP, RP, R+, R-, S+,
S-, IG
DM+, DM-, H1, H2,
HC
M3
4.4 to 5.3
(0.5 to 0.6)
Bare Wire: 18 (0.75)
Ferrule-Type: 20 (0.5)
E (G)
—
—
—
—