10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual
Page 52

10 Appendix 2 Parameter Cross Reference
52
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
Overtorque
Detection
Torque Detection
Selection 1
L6-01
0
L6-01
0
L6-01, L6-04
L6-01, L6-04
0: Disabled
0: Disabled
1: oL3 detection only
active during speed agree,
operation continues after
detection
1: oL3 detection only active during speed agree,
operation continues after detection
2: oL3 detection always
active during run,
operation continues after
detection
2: oL3 detection always active during run, operation
continues after detection
3: oL3 detection only
active during speed agree,
output shuts down on an
oL3 fault
3: oL3 detection only active during speed agree, output
shuts down on an oL3 fault
4: oL3 detection always
active during run, output
shuts down on an oL3
fault
4: oL3 detection always active during run, output shuts
down on an oL3 fault
5: UL3 detection only
active during speed agree,
operation continues after
detection
5: UL3 detection only active during speed agree,
operation continues after detection
6: UL3 detection always
active during run,
operation continues after
detection
6: UL3 detection always active during run, operation
continues after detection
7: UL3 detection only
active during speed agree,
output shuts down on an
oL3 fault
7: UL3 detection only active during speed agree, output
shuts down on an oL3 fault
8: UL3 detection always
active during run, output
shuts down on an oL3
fault
8: UL3 detection always active during run, output shuts
down on an oL3 fault
Torque Detection
Level 1
L6-02
150 %
L6-02
150 %
—
Torque Detection
Time 1
L6-03
0.1 s
L6-03
0.1 s
—
Overtorque
Detection
Torque Detection
Selection 2
L6-04
0
*
L6-04
0
*
*See the description for L6-01; replace “oL3” and “UL3” with “oL4” and “UL4”,
respectively
Torque Detection
Level 2
L6-05
150 %
L6-05
150 %
—
Torque Detection
Time 2
L6-06
0.1 s
L6-06
0.1 s
—
Torque Limit
Forward Torque
Limit
L7-01
200 %
L7-01
200 %
—
Reverse Torque
Limit
L7-02
200 %
L7-02
200 %
—
Forward
Regenerative
Torque Limit
L7-03
200 %
L7-03
200 %
—
Reverse
Regenerative
Torque Limit
L7-04
200 %
L7-04
200 %
—
Torque Limit
Integral Time
Constant
L7-06
200 ms
L7-06
200 ms
—
Torque Limit
Control Method
Selection During
Accel/Decel
L7-07
0
L7-07
0
L7-07
L7-07
0: Proportional Control
(60 Hz VT2)
0: Proportional control
1: Integral Control
(50 Hz HST1)
1: Integral control
Hardware
Protection
Internal Dynamic
Braking Resistor
Protection
Selection (ERF)
L8-01
0
L8-01
0
L8-01
L8-01
0: Not Provided
0: Disabled
1: Provided
1: Enabled
Overheat
Pre-Alarm Level
L8-02
95°C
L8-02
*
*Determined by parameters C6-01 and o2-04
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7
A1000