10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual
Page 52

10 Appendix 2 Parameter Cross Reference
52
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
Overtorque 
Detection
Torque Detection 
Selection 1
L6-01
0
L6-01
0
L6-01, L6-04
L6-01, L6-04
0: Disabled
0: Disabled
1: oL3 detection only 
active during speed agree, 
operation continues after 
detection
1: oL3 detection only active during speed agree, 
operation continues after detection
2: oL3 detection always 
active during run, 
operation continues after 
detection
2: oL3 detection always active during run, operation 
continues after detection
3: oL3 detection only 
active during speed agree, 
output shuts down on an 
oL3 fault
3: oL3 detection only active during speed agree, output 
shuts down on an oL3 fault
4: oL3 detection always 
active during run, output 
shuts down on an oL3 
fault
4: oL3 detection always active during run, output shuts 
down on an oL3 fault
5: UL3 detection only 
active during speed agree, 
operation continues after 
detection
5: UL3 detection only active during speed agree, 
operation continues after detection
6: UL3 detection always 
active during run, 
operation continues after 
detection
6: UL3 detection always active during run, operation 
continues after detection
7: UL3 detection only 
active during speed agree, 
output shuts down on an 
oL3 fault
7: UL3 detection only active during speed agree, output 
shuts down on an oL3 fault
8: UL3 detection always 
active during run, output 
shuts down on an oL3 
fault
8: UL3 detection always active during run, output shuts 
down on an oL3 fault
Torque Detection 
Level 1
L6-02
150 %
L6-02
150 %
—
Torque Detection 
Time 1
L6-03
0.1 s
L6-03
0.1 s
—
Overtorque 
Detection
Torque Detection 
Selection 2
L6-04
0
*
L6-04
0
*
*See the description for L6-01; replace “oL3” and “UL3” with “oL4” and “UL4”, 
respectively
Torque Detection 
Level 2
L6-05
150 %
L6-05
150 %
—
Torque Detection 
Time 2
L6-06
0.1 s
L6-06
0.1 s
—
Torque Limit
Forward Torque 
Limit
L7-01
200 %
L7-01
200 %
—
Reverse Torque 
Limit
L7-02
200 %
L7-02
200 %
—
Forward 
Regenerative 
Torque Limit
L7-03
200 %
L7-03
200 %
—
Reverse 
Regenerative 
Torque Limit
L7-04
200 %
L7-04
200 %
—
Torque Limit 
Integral Time 
Constant
L7-06
200 ms
L7-06
200 ms
—
Torque Limit 
Control Method 
Selection During 
Accel/Decel
L7-07
0
L7-07
0
L7-07
L7-07
0: Proportional Control 
(60 Hz VT2) 
0: Proportional control
1: Integral Control
(50 Hz HST1) 
1: Integral control
Hardware 
Protection
Internal Dynamic 
Braking Resistor 
Protection 
Selection (ERF)
L8-01
0
L8-01
0
L8-01
L8-01
0: Not Provided
0: Disabled
1: Provided
1: Enabled
Overheat 
Pre-Alarm Level
L8-02
95°C
L8-02
*
*Determined by parameters C6-01 and o2-04
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7
A1000