11 appendix 3 terminal size and wire gauge, Table 20, R/ 1, / 2 – Yaskawa F7 to A1000 User Manual
Page 60

11 Appendix 3 Terminal Size and Wire Gauge
60
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
Table 20
3-Phase 400 V Class Main Circuit Terminal Size and Gauge
A1000
2A0360
R/L1, S/L2, T/L3
M12
32 to 40
(283 to 354)
4/0 to 600
250×2P
U/T1, V/T2, W/T3
M12
32 to 40
(283 to 354)
4/0 to 600
4/0×2P
-, +1
M12
32 to 40
(283 to 354)
250 to 600
—
+3
M10
18 to 23
(159 to 204)
3/0 to 600
—
M12
32 to 40
(283 to 354)
1 to 350
1
F7
2110
R/L1, S/L2, T/L3,
-, +1, R1/L11, S1/L21,
T1/L31
M12
31.4 to 39.2
(276.2 to 344.8)
N/A
350×2P
U/T1, V/T2, W/T3
M12
31.4 to 39.2
(276.2 to 344.8)
N/A
300×2P
+3
M8
8.8 to 10.8
(77.4 to 95.0)
N/A
—
M12
31.4 to 39.2
(276.2 to 344.8)
N/A
300×2P
r/ 1, / 2
M4
1.3 to 1.4
(11.4 to 12.3)
N/A
16
A1000
2A0415
R/L1, S/L2, T/L3
M12
32 to 40
(283 to 354)
250 to 600
350×2P
U/T1, V/T2, W/T3
M12
32 to 40
(283 to 354)
300 to 600
300×2P
-, +1
M12
32 to 40
(283 to 354)
300 to 600
—
+3
M10
18 to 23
(159 to 204)
3/0 to 600
—
M12
32 to 40
(283 to 354)
1 to 350
1
Series
Model
Terminal Signal
Terminal
Screw
Tightening Torque
N ・ m (lb.in.)
Wire Range AWG,
kcmil
Recommended
Gauge AWG, kcmil
F7
40P4
40P7
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2,
M4
1.2 to 1.5
(10.6 to 13.2)
14 to 10
14
A1000
4A0002
4A0004
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2,
M4
1.2 to 1.5
(10.6 to 13.2)
14 to 10
14, 12 (Ground)
F7
41P5
42P2
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2,
M4
1.2 to 1.5
(10.6 to 13.2)
14 to 10
14
A1000
4A0005
4A0007
4A0009
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2
M4
1.2 to 1.5
(10.6 to 13.2)
14 to 10
14
M4
1.2 to 1.5
(10.6 to 13.2)
14 to 10
10
F7
43P7
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2
M4
1.2 to 1.5
(10.6 to 13.2)
14 to 10
12
M4
1.2 to 1.5
(10.6 to 13.2)
14 to 10
14
Series
Model
Terminal Signal
Terminal
Screw
Tightening Torque
N ・ m (lb.in.)
Wire Range
AWG, kcmil
Recommended
Gauge AWG, kcmil