10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual
Page 53

10 Appendix 2 Parameter Cross Reference
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
53
Hardware
Protection
Overheat Pre-
Alarm Operation
Selection
L8-03
3
L8-03
3
L8-03
L8-03
0: Ramp to stop
0: Ramp to stop
1: Coast to stop
1: Coast to stop
2: Fast Stop
2: Fast Stop
3: Alarm Only
3: Continue operation (Alarm triggered)
—
4: Continue operation at reduced speed as set in L8-19
Input Phase Loss
Protection
Selection
L8-05
0
L8-05
1
L8-05
L8-05
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Output Open-
Phase Protection
Selection
L8-07
0
L8-07
1
L8-07
L8-07
0: Disabled
0: Disabled
1: Enabled (triggered by a
single phase loss)
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered
when two phases are lost)
2: Enabled (triggered when two phases are lost)
Output Ground
Fault Detection
Selection
L8-09
1
L8-09
1*
L8-09
L8-09
0: Disabled
0: Disabled
1: Enabled
1: Enabled
*Determined by parameters C6-01 and o2-04
Heatsink Cooling
Fan Operation
Selection
L8-10
0
L8-10
0
L8-10
L8-10
0: During run only
0: During run only
1: Fan always on
1: Fan always on
Heatsink Cooling
Fan Operation
Delay Time
L8-11
60 s
L8-11
60 s
—
Ambient
Temperature
Setting
L8-12
45°C
L8-12
40°C
Set the ambient temperature where the drive is being used.
oL2 Characteristics
Selection at Low
Speeds
L8-15
1
L8-15
1
L8-15
L8-15
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Soft CLA
Selection
L8-18
1
L8-18
1
L8-18
L8-18
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Hunting
Prevention
Function
Hunting
Prevention
Function Selection
n1-01
1
n1-01
1
n1-01
n1-01
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Hunting
Prevention Gain
Setting
n1-02
1.00
n1-02
1.00
—
Speed Feedback
Detection Control
Function
Speed Feedback
Detection Control
(AFR) Gain
n2-01
1.00
n2-01
1.00
—
Speed Feedback
Detection Control
(AFR) Time
Constant
n2-02
50 ms
n2-02
50 ms
—
Speed Feedback
Detection Control
(AFR) Time
Constant 2
n2-03
750 ms
n2-03
750 ms
—
High slip Braking
High-Slip Braking
Deceleration
Frequency Width
n3-01
5 %
n3-01
5 %
—
High-Slip Braking
Current Limit
n3-02
150 %
n3-02
150 %
*
*Upper limit is determined by L8-38 and C6-01
High-Slip Braking
Dwell Time at Stop
n3-03
1.0 s
n3-03
1.0 s
—
High-Slip Braking
Overload Time
n3-04
40 s
n3-04
40 s
—
Feed Forward
Control
Feed Forward
Control Selection
—
—
n5-01
0
New for the A1000.
Motor
Acceleration Time
---
—
n5-02
*
*Determined by C6-01, o2-04, and E5-01.
New for the A1000.
Feed Forward
Control Ratio Gain
—
—
n5-03
1.00
New for the A1000.
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7
A1000