10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual
Page 49

10 Appendix 2 Parameter Cross Reference
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
49
MEMOBUS
Communication
Drive Node
Address
H5-01
1F
H5-01
1F
—
Communication
Speed Selection
H5-02
3
H5-02
3
H5-02
H5-02
0: 1200 bps
0: 1200 bps
1: 2400 bps
1: 2400 bps
2: 4800 bps
2: 4800 bps
3: 9600 bps
3: 9600 bps
4: 19200 bps
4: 19200 bps
—
5: 38400 bps
—
6: 57600 bps
—
7: 76800 bps
—
8: 115200 bps
Communication
Parity Selection
H5-03
0
H5-03
0
H5-03
H5-03
0: No parity
0: No parity
1: Even parity
1: Even parity
2: Odd parity
2: Odd parity
Stopping Method
After
Communication
Error
H5-04
3
H5-04
0
H5-04
H5-04
0: Ramp to stop
0: Ramp to stop
1: Coast to stop
1: Coast to stop
2: Fast Stop
2: Fast Stop
3: Alarm Only
3: Alarm Only
Communication
Fault Detection
Selection
H5-05
1
H5-05
0
H5-05
H5-05
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Drive Transmit
Wait Time
H5-06
5 ms
H5-06
5 ms
—
RTS Control
Selection
H5-07
1
H5-07
1
H5-07
H5-07
0: Disabled
(RTS always on)
0: Disabled
(RTS always on)
1: Enabled
(RTS enabled during send
only)
1: Enabled
(RTS enabled during send only)
Unit Selection for
MEMOBUS
Register 0025H
H5-10
0
H5-10
0
H5-10
H5-10
0: 0.1 V units
0: 0.1 V units
1: 1 V units
1: 1 V units
Pulse Train I/O
Pulse Train Input
Function Selection
H6-01
0
H6-01
0
H6-01
H6-01
0: Frequency reference
0: Frequency reference
1: PID feedback value
1: PID feedback value
2: PID setpoint value
2: PID setpoint value
—
3: V/f Control with Simple PG feedback
Pulse Train I/O
Pulse Train Input
Scaling
H6-02
1440 Hz
H6-02
1440 Hz
—
Pulse Train Input
Gain
H6-03
100.0 %
H6-03
100.0 %
—
Pulse Train Input
Bias
H6-04
0.0 %
H6-04
0.0 %
—
Pulse Train Input
Filter Time
H6-05
0.10 s
H6-05
0.10 s
—
Pulse Train
Monitor Selection
H6-06
2
H6-06
102
H6-06
H6-06
01: Frequency reference
101: Frequency reference
02: Output frequency
102: Output frequency
05: Motor speed
105: Motor speed
20: Output frequency after
soft start
116: Output frequency after soft start
24: PID feedback
501: PID feedback
36: PID input amount
502: PID input amount
Pulse Train
Monitor Scaling
H6-07
1440 Hz
H6-07
1440 Hz
—
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7