10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual
Page 50

10 Appendix 2 Parameter Cross Reference
50
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
Motor Protection
Function
Motor Overload
Protection
Selection
L1-01
1
L1-01
1
*
L1-01
L1-01
0: Disabled
0: Disabled
1: Standard fan cooled
1: General-purpose motor
2: Standard blower cooled
2: Drive-dedicated motor with a speed range of 1:10
3: Vector motor
3: Vector motor with a speed range of 1:100
—
4: PM motor with variable torque
—
5: PM motor with constant torque control
—
6: General purpose motor (50 Hz)
*Determined by parameter A1-02
Motor Overload
Protection Time
L1-02
8.0 min.
L1-02
1.0 min.
—
Motor Overheat
Alarm Operation
Selection
L1-03
3
L1-03
3
L1-03
L1-03
0: Ramp to stop
0: Ramp to stop
1: Coast to stop
1: Coast to stop
2: Fast Stop
2: Fast Stop
3: Alarm Only
3: Alarm Only
Motor Protection
Function
Motor Overheat
Fault Operation
Selection
L1-04
1
L1-04
1
L1-04
L1-04
0: Ramp to stop
0: Ramp to stop
1: Coast to stop
1: Coast to stop
2: Fast Stop
2: Fast Stop
Motor Temperature
Input Filter Time
L1-05
0.20 s
L1-05
0.20 s
—
Momentary Power
Loss Process
Momentary Power
Loss Detection/
Operation
Selection
L2-01
0
L2-01
0
L2-01
L2-01
0: Disabled
0: Disabled
1: Power Loss Ride Thru
Time
1: Recover within the time set in L2-02
2: CPU Power Active
2: Recover as long as CPU Power Active
—
3: KEB deceleration for time set in L2-02
—
4: KEB deceleration as long as CPU has power.
—
5: KEB deceleration to stop.
Momentary Power
Loss Ride-Thru
Time
L2-02
*
L2-02
*
*Dependent on kVA and parameters C6-01 and o2-04
Momentary Power
Loss Minimum
Baseblock Time
L2-03
*
L2-03
*
*Dependent on kVA and parameters C6-01 and o2-04
Momentary Power
Loss Voltage
Recovery Ramp
Time
L2-04
*
L2-04
*
*Dependent on kVA and parameters C6-01 and o2-04
Undervoltage
Detection Level
L2-05
190 V
L2-05
190 V
380 V for a 400 class drive.
But if E1-01 is set lower than 400, then for set 350 V for A1000.
KEB Deceleration
Time
L2-06
0.0 s
L2-06
0.0 s
Sets the deceleration time during KEB.
KEB Acceleration
Time After Power
Recovery
L2-07
0.0 s
L2-07
0.0 s
—
Momentary Power
Loss Process
Frequency Gain at
KEB Start
L2-08
100 %
L2-08
100 %
—
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7
A1000