10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual
Page 39
10 Appendix 2 Parameter Cross Reference
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
39
PG speed Control
Card
PG Division Rate
(PG Pulse
Monitor)
F1-06
1
F1-06
1
Enabled when using the PG-B2 option card.
Integral Function
During Accel/
Decel Selection
F1-07
0
C5-12
0
F1-07
C5-12
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Overspeed
Detection Level
F1-08
115 %
F1-08
115 %
—
Overspeed
Detection Delay
Time
F1-09
0.0 s
F1-09
*
*Determined by parameter A1-02
Excessive Speed
Deviation
Detection Level
F1-10
10%
F1-10
10 %
—
Excessive Speed
Deviation
Detection Delay
Time
F1-11
0.5 s
F1-11
0.5 s
—
Number of PG
Gear Teeth 1
F1-12
0
F1-12
0
—
Number of PG
Gear Teeth 2
F1-13
0
F1-13
0
—
PG Open-Circuit
Detection Time
F1-14
2.0 s
F1-14
2.0 s
—
Analog Command
Card
AI-14 Input
Selection
F2-01
0
F2-01
0
F2-01
F2-01
0:
Separate channels
0:
Separate channels
1: Sum of channel values
1: Sum of channel values
Digital Command
Card
DI-08/DI-16H2
Input Selection
F3-01
0
F3-01
0
*The digital option card determines the setting
DI-08: 0 (8 bit)
DI-16H: Set switch S1 to determine input signal:
S1 switch 1: 2 (16 bit)
S1 switch S1: 1 (12 bit)
F3-01
F3-01
F3-03
0: BCD 1% units
0: BCD 1% units
0: 8 bit
1: BCD 0.1% units
1: BCD 0.1% units
1: 12 bit
2: BCD 0.01% units
2: BCD 0.01% units
2: 16 bit
Digital Input
Option DI-A3 Data
Length Selection
─
─
F3-03
2
*
3: BCD 1 Hz units
3: BCD 1 Hz units
—
4: BCD 0.1 Hz units
4: BCD 0.1 Hz units
—
5: BCD 0.01 Hz units
5: BCD 0.01 Hz units
—
6: BCD customized
setting (5-digit), 0.01 Hz
units
6: BCD customized
setting (5-digit), 0.02 Hz
units
—
7: Binary input
7: Binary input
—
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7
A1000