10 appendix 2 parameter cross reference, Parameter setting procedure, Appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual
Page 30: Parameter setting procedure 1, Table 18 parameter cross reference
30
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
10 Appendix 2 Parameter Cross Reference
10
Appendix 2 Parameter Cross Reference
Parameter Setting Procedure
1.
This document lists the information needed to upgrade from F7 to a new A1000 drive. The A1000 drive must be set for Heavy Duty. First, set A1000
parameter C6-01 to 0.
2.
Check all F7 parameters that have been changed from their default settings by using the Modified Constants Menu.
3.
Set the same control mode used for F7 to A1000.
4.
Set parameters as described in this section.
Note: Default Values in the table below are listed for A1000 200 V Class 0.4 kW Drive Using Open Loop Vector Control
Table 18 Parameter Cross Reference
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7
A1000
Environment
Settings
Language
Selection
A1-00
0
A1-00
0
A1-00
A1-00
0: English
0: English
1: Japanese
1: Japanese
2: German
2: German
3: French
3: French
4: Italian
4: Italian
5: Spanish
5: Spanish
6: Portuguese
6: Portuguese
—
7: Chinese
Access Level
Selection
A1-01
2
A1-01
2
A1-01
A1-01
0: Operation only
(monitors only)
0: Operation only (monitors only)
1: User Parameters
1: User Parameters *
2: All parameters
2: All parameters
*Set parameters A2-01 through A2-32
Environment
Settings
Control Method
Selection
A1-02
2
A1-02
2
A1-02
A1-02
0: V/f Control
0: V/f Control
1: V/f w/PG Control
1: V/f w/PG Control
2: Open Loop Vector
2: Open Loop Vector
3: Flux Vector
3: Closed Loop Vector
—
5: Open Loop Vector for PM
—
6: Advanced Open Loop Vector for PM
—
7: Closed Loop Vector for PM
Initialize
Parameters
A1-03
0
A1-03
0
A1-03
A1-03
0: No initialization
0: No initialization
1110: User initialize
1110: User initialize
2220: 2-wire sequence
2220: 2-wire sequence
3330: 3-wire sequence
3330: 3-wire sequence
—
5550: Reset OPE04
Password
A1-04
0
A1-04
0000
—
Password Setting
A1-05
0
A1-05
0000
—
User Parameters
A2-01 to
A2-32
—
A2-01 to
A2-32
—
If setting A1-01 to 1, refer to the manual and set parameters A2-01 top A2-32.