2 f7 to a1000 feature specifications, F7 to a1000 feature specifications, Table 2 feature specifications – Yaskawa F7 to A1000 User Manual
Page 5: 1> hd = heavy duty, nd = normal duty

2 F7 to A1000 Feature Specifications
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
5
2
F7 to A1000 Feature Specifications
Table 2 Feature Specifications
Feature
Item
Yaskawa F7
Yaskawa A1000
HP Range
200 V
240V 0.5 to 150 HP (HD) 0.5 to 175 HP (ND)
<1> HD = Heavy Duty, ND = Normal Duty
240 V 0.75 to 150 HP (HD) 0.75 to 175 HP (ND)
400 V
480V 0.5 to 500 HP (HD) 0.5 to 600 HP (ND)
480 V 0.75 to 900 HP (HD) 0.75 to 1000 HP (ND)
600 V
—
600 V 2 to 250 HP (ND)
Input Voltage
Rated Voltage
3-phase, 200-240 Vac
3-phase, 380-480 Vac
3-phase, 200-240 Vac
3-phase, 380-480 Vac
3-phase, 500-600 Vac
Motor types
—
Induction
Induction, Permanent Magnet
PWM Carrier Frequency
Range
See Appendix 1
See Appendix 1
Maximum Output Frequency
Hz
300 Hz (HD) 400 Hz (ND)
1000 Hz optional
400 Hz (1000 Hz optional)
Keypad Design
Display
5 Line X 16 Character LCD
5 Line X 16 Character LCD
Copy Function
Yes
Yes
Digital Input Terminal
NPN/PNP
Switchable NPN/PNP
Switchable NPN/PNP
Digital output Terminal
Open Collector
0
0
Relay Output
3 x Form A, 1 x Form C
3 x Form A, 1 x Form C
Analog Output
Output Level
2 channels
with independent level selections
0-10 V (10 bit plus sign) or
–10-+10 V or 10 bit plus sign or 4-20 ma 10 bit
2 channels with independent level selections
0-10 V (10 bit plus sign) or
–10-+10 V or 10 bit plus sign or 4-20 ma 10 bit
Pulse Input
Qty:
1
1
Input Frequency
1-32 kHz
1-32 kHz
Pulse Output
Qty:
1
1
Output Frequency
1-32 kHz
1-32 kHz
Quick Disconnect Terminals
Type
Yes
Yes
Auto Tuning
Methods
Rotating, Stationary
Rotating, Stationary, Continuous, Inertia /ASR
Preset Speeds
Qty.
17
17
Speed Search
Bi/Uni-Directional
Bi-Directional
Bi-Directional
Method
Current/Speed
Current/Speed Estimation
Auto Restart
Time Between Attemps
0.0 – 5.0 sec (selectable)
0.0 – 5.0 sec (selectable)
Energy Savings Mode
Man/Auto
Man/Auto
Man/Auto
DC Injection Function
At Start/At Stop
At Start/At Stop +HSB during stop
At Start/At Stop +HSB during stop
Braking Function
DB Transistor
Built-in to 25 HP
Built-in to 40 HP (HD)
Special
High Slip Braking
High Slip/Over-excitation Braking
Cooling Fan On/Off Control
Power/Run
Run Based
Selectable Always Active/During Run
Timer Function
On/Off Delay
On/Off Delay (0-3000 s)
On/Off Delay (0-3000 s)
Fault Code Additions
—
10 additional
10 with elapsed time stamp
Torque Limit/Current Limit/
Stall Prevention
—
Stall Prevention
During Accel/Run/Decel (V/F)
Torque Limit in 4 Quadrants (Vector)
Software Current Limit (HD=150 %, ND=120 %)
Stall Prevention
During Accel/Run/Decel (V/F)
Torque Limit in 4 Quadrants (Vector)
Software Current Limit (HD=150 %, ND=120 %)
Harmonic Counter Measures
—
12 Pulse: 30 HP and Above
Filters/Reactors (Options)
Filters/Reactors (Options)
Built-In DC Bus Reactor
240 Vac:30-150 HP (HD)
480 Vac: 30-500 HP (HD)
240 Vac: 30-175 HP (ND)
480 Vac: 30-1000 HP (ND)
600 Vac: 30-250 HP (ND)
Ambient Temperature
ºC
-10ºC ~ +40ºC (IP21)
-10ºC ~ +45ºC (IP00)
-10 to +50°C (Open Chassis Installation)
-10 to +40°C (Chassis with zero side clearance, or Type 1)
Storage Temperature
ºC
-20ºC ~ +60ºC
-20ºC ~ +60ºC
Network Communications
Standard
Modbus RTU via terminal I/O RS485/422
Modbus RTU
via terminal I/O RS485/422
Optional
DeviceNet, Profibus-DP, ControlNet, Ethernet
DeviceNet, Profibus-DP, ProfiNet, Ethernet,
Modbus TCP/IP, Mechatrolink
Unique Feature/Function
—
HSB – High Slip Braking
Over-excitation Braking