10 Appendix 2 Parameter Cross Reference
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
51
Stall Prevention
Function
Stall Prevention
Selection during
Acceleration
L3-01
1
L3-01
1
L3-01
L3-01
0: Disabled
0: Disabled
1: General purpose
1: General purpose
2: Intelligent
2: Intelligent
Stall Prevention
Level during
Acceleration
L3-02
*
L3-02
150 %
**
*Varies by Duty Rating
**Upper limit is determined by C6-01 and L8-38.
Stall Prevention
Limit during
Acceleration
L3-03
50 %
L3-03
50 %
—
Stall Prevention
Selection during
Deceleration
L3-04
1
L3-04
1
L3-04
L3-04
0: Disabled
0: Disabled
1: General purpose
1: General purpose
2: Intelligent
2: Intelligent
3: Stall Prevention with
braking resistor
3: Stall Prevention with braking resistor
—
4: Overexcitation Deceleration
—
5: Overexcitation Deceleration 2
Stall Prevention
Selection during
Run
L3-05
1
L3-05
1
L3-05
L3-05
0: Disabled
0: Disabled
1: Enabled (Decel Time 1) 1: Enabled (Decel Time 1)
2: Enabled (Decel Time 2) 2: Enabled (Decel Time 2)
Stall Prevention
Level during Run
L3-06
*
L3-06
**
*Varies by duty rating (Defaults:HD = 150 %, ND = 120 %)
**Upper limit is determined by C6-01 and L8-38.
Overvoltage
Supression
Function Selection
L3-11
0
L3-11
0
L3-11
L3-11
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Stall Prevention
Function
F7: Overvoltage
Suppression
Voltage Level
A1000: Target DC
Bus Voltage for
Overvoltage
Suppression and
Stall Prevention
L3-12
380 V
*
L3-17
370 V
*
*Double values for 400 V class drives.
Frequency
Detection
Speed Agreement
Detection Level
L4-01
0.0 Hz
L4-01
0.0 Hz
—
Speed Agreement
Detection Width
L4-02
2.0 Hz
L4-02
*
*Dependent on parameter A1-02
Speed Agreement
Detection Level (+/
-)
L4-03
0.0 Hz
L4-03
0.0 Hz
—
Speed Agreement
Detection Width
(+/-)
L4-04
2.0 Hz
L4-04
*
*Dependent on parameter A1-02
Frequency
Reference Loss
Detection
Selection
L4-05
0
L4-05
0
L4-05
L4-05
0: Stop
0: Stop
1: Run at L4-06 PrevRef
1: Run at the level set to L4-06
In A1000, the setting range for the frequency reference when the reference is lost
(L4-06) is 0 to 100 % (default: 80 %)
Reference
Detection
Frequency
Reference Level at
Loss Frequency
L4-06
80.0 %
L4-06
80.0 %
—
Fault Restart
Number of Auto
Restart Attempts
L5-01
0 times
L5-01
0 times
—
Auto Restart
Operation
Selection
L5-02
0
L5-02
0
L5-02
L5-02
0: No Fault Relay
0: Fault output not active
1: Fault Relay Active
1: Fault output active during restart attempt
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7