10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual
Page 48

10 Appendix 2 Parameter Cross Reference
48
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
Analog Input
Terminal A3
Function Selection
H3-05
2
H3-06
2
10: FWD torque limit
10: FWD torque limit
11: REV torque limit
11: REV torque limit
12: Torque limit during
regen
12: Torque limit during regen
13: Torque ref/Torque
limit during Torque
Control
13: Torque ref/Torque limit
14: Torque compensation
14: Torque compensation
15: Fwd/Rev torque limit
15: General torque limit
—
16: Differential PID feedback
1F: Not used
1F: Through-mode
—
30 to 32: DriveWorksEZ, Analog input 1 to 3
Terminal A3 Gain
Setting
H3-06
100.0 %
H3-07
100.0 %
—
Terminal A3 Bias
Setting
H3-07
0.0 %
H3-08
0.0 %
—
Terminal A2
Signal Level
Selection
H3-08
2
H3-09
2
H3-08
H3-09
0: 0 to 10 V
0: 0 to +10 V (with lower limit)
1: -10 to 10 V
1: -10 to +10 V (no lower limit)
2: 4 to 20 mA
2: 4 to 20 mA
—
3: 0 to 20 mA
Terminal A2
Function Selection
H3-09
0
*
H3-10
0
*
*For A1000, see the description for H3-06.
Terminal A2 Gain
Setting
H3-10
100.0 %
H3-11
100.0 %
—
Terminal A2 Bias
Setting
H3-11
0.0 %
H3-12
0.0 %
—
Analog Input Filter
Time Constant
H3-12
0.03 s
H3-13
0.03 s
—
Multi-Function
Analog Output
Analog Output 1
Terminal FM
Monitor Selection
H4-01
2
*
H4-01
102
*
*See the description for F4-01
Analog Output 1
Terminal FM Gain
H4-02
100 %
H4-02
100.0 %
—
Analog Output 1
Terminal FM Bias
H4-03
0.0 %
H4-03
0.0 %
—
Analog Output 2
Terminal AM
Selection
H4-04
3
*
H4-04
103
*
*See the description for F4-01
Analog Output 2
Terminal AM Gain
H4-05
50.0 %
H4-05
50.0 %
—
Analog Output 2
Terminal AM Bias
H4-06
0.0 %
H4-06
0.0 %
—
Analog Output 1
Signal Level (FM)
Selection
H4-07
0
H4-07
0
H4-07
H4-07
0: 0 to +10 V output
0: 0 to +10 Vdc output
1: -10 to 10 Vdc output
1: -10 to 10 Vdc output
2: 4 to 20 mA
2: 4 to 20 mA
Analog Output 2
Signal Level (AM)
Selection
H4-08
0
H4-08
0
H4-08
H4-08
0: 0 to +10 V output
0: 0 to +10 Vdc output
1: -10 to 10 Vdc output
1: -10 to 10 Vdc output
2: 4 to 20 mA
2: 4 to 20 mA
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7