10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual
Page 31

10 Appendix 2 Parameter Cross Reference
YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide
31
Operation Mode
Selection
Frequency
Reference
Selection
b1-01
1
b1-01
1
b1-01
b1-01
0: Operator
0: Operator
1: Control circuit terminal
(analog input)
1: Control circuit terminal
(analog input)
2: MEMOBUS comm.
2: MEMOBUS comm.
3: Option card
3: Option card
4: Pulse train input
4: Pulse train input
Operation Method
Selection
b1-02
1
b1-02
1
b1-02
b1-02
0: Operator
0: Operator
1: Control circuit terminal
1: Control circuit terminal
2: MEMOBUS comm.
2: MEMOBUS comm.
3: Option card
3: Option card
Stopping Method
Selection
b1-03
0
b1-03
0
b1-03
b1-03
0: Ramp to stop
0: Ramp to stop
1: Coast to stop
1: Coast to stop
2: DC Injection Braking
2: DC Injection Braking
3: Coast to stop with timer 3: Coast to stop with timer
Operation Mode
Selection
Reverse Operation
Selection
b1-04
0
b1-04
0
b1-04
b1-04
0: Reverse enabled
0: Reverse enabled
1: Reverse disabled
1: Reverse disabled
2: Exchange Phase
—
Operation
Selection for
Setting E1-09 or
Less
b1-05
0
b1-05
0
b1-05
b1-05
0: Run at frequency
reference
0: Run at frequency reference
1: Shut off drive output
1: Shut off drive output
2: Operate by E1-09
2: Operate by E1-09
3: Zero speed
3: Zero speed
Digital Input Scan
Time
b1-06
1
b1-06
1
b1-06
b1-06
0: 2 ms - 2 scans
0: 1 ms - 1 scan
1: 5 ms - 2 scans
1: 1 ms - 2 scans
Operation
Selection After
Switching to
Remote Mode
b1-07
0
b1-07
0
b1-07
b1-07
0: Cycle Run command
0: Cycle Run command
1: Accept external Run
cmd
1: Accept external Run cmd
Run Command
Selection while in
Programming
Mode
b1-08
0
b1-08
0
b1-08
b1-08
0: Disabled.
0: Disabled.
1: Enabled - Run cmd
always accepted
1: Enabled - Run cmd always accepted
Run Command at
Power Up
─
─
b1-17
0
0: Prohibited 1: Allowed
Change b1-17 to 1 to match F7 (Caution: drive will run at power on)
DC Injection
Braking
DC Injection
Braking Start
Frequency
b2-01
0.5 Hz
b2-01
0.5 Hz*
*Determined by parameter A1-02, Control Method Selection
DC Injection
Braking current
b2-02
50%
b2-02
50 %
—
DC Injection
Braking Time at
Start
b2-03
0.00 s
b2-03
0.00 s
—
DC Injection
Braking Time at
Stop
b2-04
0.00 s
b2-04
0.50 s
*
*Determined by the control mode selected.
Magnetic Flux
Compensation
Value
b2-08
0%
b2-08
0%
—
Parameter Name
F7
A1000
Setting
Parameter
Default
Parameter
Default
F7
A1000