beautypg.com

4 insulation monitoring, 5 device-internal values, Insulation monitoring – SMA SC 500HE-20 User Manual

Page 98: Device-internal values

background image

12  Parameters

SMA Solar Technology AG

98

SCxxxHE-20-BE-BEN111210

Operating Manual

12.1.4 Insulation Monitoring

12.1.5 Device-Internal Values

Name

Description

Value/Range

Explanation

Default

value

IsoErrIgn

*

These parameters can only be changed after the installer password has been entered.

Enable insulation
error detection

Off

Deactivated

On

On

Activated

Name

Description

Value/Range

Explanation

Default

value

PvPwrMinTr

Threshold value for
starting the MPP
tracker

0 kW … 20 kW

20 kW

PvPwrMinTrT

Timeout for starting
the MPP tracker

1 s … 600 s

10 s

PvVtgStrLevMin

*

Threshold value for
switching to feed-in
operation

0 V … 1 200 V SC 500HE-20

480 V

0 V … 1 200 V SC 630HE-20

610 V

0 V … 1 200 V SC 720HE-20

675 V

0 V … 1 200 V SC 760HE-20

715 V

0 V … 1 200 V SC 800HE-20

760 V

PVStrT

Target status switches
from "Wait-PV" to
"Grid-Connect" when
timer elapses

1 s … 300 s

90 s

VArGra

**

Gradient of active
power change
(VAr/s)

0% … 20%

20%

RemMntSvc

Activate plant
maintenance

Off

Plant maintenance off

Off

On

Plant maintenance on

Serial Number

*

Inverter serial number

0 …

2147483647

---

CntrySet

*

Specify the country

country-specific

---

CardFunc

*

MMC/SD card
function

---

Service information
for SMA Solar
Technology AG

0

ForcedWrite

StoFailStt

DtSet

Date

20060101…

20991231

0

TmSet

Time

0 … 235959

0

This manual is related to the following products: