4 insulation monitoring, 5 device-internal values, Insulation monitoring – SMA SC 500HE-20 User Manual
Page 98: Device-internal values
12 Parameters
SMA Solar Technology AG
98
SCxxxHE-20-BE-BEN111210
Operating Manual
12.1.4 Insulation Monitoring
12.1.5 Device-Internal Values
Name
Description
Value/Range
Explanation
Default
value
IsoErrIgn
*
*
These parameters can only be changed after the installer password has been entered.
Enable insulation
error detection
Off
Deactivated
On
On
Activated
Name
Description
Value/Range
Explanation
Default
value
PvPwrMinTr
Threshold value for
starting the MPP
tracker
0 kW … 20 kW
20 kW
PvPwrMinTrT
Timeout for starting
the MPP tracker
1 s … 600 s
10 s
PvVtgStrLevMin
*
Threshold value for
switching to feed-in
operation
0 V … 1 200 V SC 500HE-20
480 V
0 V … 1 200 V SC 630HE-20
610 V
0 V … 1 200 V SC 720HE-20
675 V
0 V … 1 200 V SC 760HE-20
715 V
0 V … 1 200 V SC 800HE-20
760 V
PVStrT
Target status switches
from "Wait-PV" to
"Grid-Connect" when
timer elapses
1 s … 300 s
90 s
VArGra
**
Gradient of active
power change
(VAr/s)
0% … 20%
20%
RemMntSvc
Activate plant
maintenance
Off
Plant maintenance off
Off
On
Plant maintenance on
Serial Number
Inverter serial number
0 …
2147483647
---
CntrySet
Specify the country
country-specific
---
CardFunc
MMC/SD card
function
---
Service information
for SMA Solar
Technology AG
0
ForcedWrite
StoFailStt
DtSet
Date
20060101…
20991231
0
TmSet
Time
0 … 235959
0