12.1.2 Grid Monitoring/Grid Limits

PwrApLimitPrio

**

Prioritization of
active power or
reactive power

PrioPwrRt

Prioritization of reactive
power

PrioPwrRt

PrioPwrAt

Prioritization of active
power

SDLimComSrc

Selection of the
SDELimit source

CAN

SC-COM interface

UART

UART

Via SMA Net

These parameters are only visible if the installer password is entered.

** 

These parameters can only be changed if the installer password is entered.

Name

Description

Range

Explanation

Default

value

VRtg

*

Nominal line voltage
of the power
distribution grid

1 V … 70 000 V

20 000 V

VCtlMax

*

Threshold value for
overvoltage
activation level 3

100% … 150%

country-

specific

VCtlMaxTm

*

Activation time for
overvoltage level 3

0 ms …

1 000 000 ms

country-

specific

VCtlhhLim

*

Threshold value for
overvoltage
activation level 2

130% … 500%

country-

specific

VCtlhhLimTm

*

Activation time for
overvoltage level 2

0 ms …

1 000 000 ms

country-

specific

VCtlhLim

*

Threshold value for
overvoltage
activation level 1

100% … 150%

country-

specific

VCtlhLimTm

*

Activation time for
overvoltage level 1

0 ms …

1 000 000 ms

country-

specific

VCtllLim

*

Threshold value for
undervoltage
activation level 1

0% … 100%

country-

specific

VCtllLimTm

*

Activation time for
undervoltage level 1

0 ms …

1 000 000 ms

country-

specific

VCtlllLim

*

Threshold value for
undervoltage
activation level 2

0% … 100%

country-

specific

Name

Description

Value/Range

Explanation

Default

value