2 grid monitoring/grid limits, Grid monitoring/grid limits, Pfabsmin – SMA SC 500HE-20 User Manual
Page 95: Wgra
SMA Solar Technology AG
12 Parameters
Operating Manual
SCxxxHE-20-BE-BEN111210
95
12.1.2 Grid Monitoring/Grid Limits
PwrApLimitPrio
Prioritization of
active power or
reactive power
PrioPwrRt
Prioritization of reactive
power
PrioPwrRt
PrioPwrAt
Prioritization of active
power
SDLimComSrc
Selection of the
SDELimit source
CAN
SC-COM interface
UART
UART
Via SMA Net
*
These parameters are only visible if the installer password is entered.
**
These parameters can only be changed if the installer password is entered.
Name
Description
Range
Explanation
Default
value
VRtg
*
Nominal line voltage
of the power
distribution grid
1 V … 70 000 V
20 000 V
Threshold value for
overvoltage
activation level 3
100% … 150%
country-
specific
Activation time for
overvoltage level 3
0 ms …
1 000 000 ms
country-
specific
VCtlhhLim
Threshold value for
overvoltage
activation level 2
130% … 500%
country-
specific
VCtlhhLimTm
Activation time for
overvoltage level 2
0 ms …
1 000 000 ms
country-
specific
Threshold value for
overvoltage
activation level 1
100% … 150%
country-
specific
Activation time for
overvoltage level 1
0 ms …
1 000 000 ms
country-
specific
Threshold value for
undervoltage
activation level 1
0% … 100%
country-
specific
Activation time for
undervoltage level 1
0 ms …
1 000 000 ms
country-
specific
Threshold value for
undervoltage
activation level 2
0% … 100%
country-
specific
Name
Description
Value/Range
Explanation
Default
value