beautypg.com

SMA SC 500HE-20 User Manual

Page 92

background image

12  Parameters

SMA Solar Technology AG

92

SCxxxHE-20-BE-BEN111210

Operating Manual

VArCtlVol

Sets the reactive power
depending on the grid
voltage

VArCtlVolHystTb Sets the reactive power

depending on the grid
voltage (Q = f(U)
characteristic curve)

Q-VAr

Reactive power in
kVAr

− 245 kVAr …

245 kVAr

SC 500HE-20

0

− 310 kVAr …

310 kVAr

SC 630HE-20

‒346 kVAr …

346 kVAr

SC 720HE-20

− 365 kVAr …

365 kVAr

SC 760HE-20

− 385 kVAr …

385 kVAr

SC 800HE-20

Q-VArNom

Reactive power
in %

− 100% … 100%

0

PF-PF

Displacement
power factor cos φ
The lower limit is
defined by
parameter
"PFAbsMin".

0.9 … 1

1

PF-PFExt

Excitation of the
displacement
power factor cos φ.

OvExt

Overexcited

OvExt

UnExt

Underexcited

PF-PFStr

**

Displacement
power factor cos φ
at characteristic
curve point 1,
The lower limit is
defined by
parameter
"PFAbsMin"

0.5 … 1

0.9

Name

Description

Value/Range

Explanation

Default

value

This manual is related to the following products: