SMA SC 500HE-20 User Manual
Page 78

10 Troubleshooting
SMA Solar Technology AG
78
SCxxxHE-20-BE-BEN111210
Operating Manual
3803
Error message
< DC overcurrent >
– The current of the PV array is too high.
Measure
< Check DC generator >
– Check DC input current.
– Check module wiring and plant design.
4003
Error message
< Reverse currents or input polarity reversed >
– Reverse currents detected in the PV array or DC connection polarity is
reversed.
Measure
< Check DC generator >
– Check PV modules for short circuit.
– Check module wiring and plant design.
– Make sure the DC terminals have the correct polarity.
Error no.
Error message, cause of error and corrective measure