beautypg.com

SMA SC 500HE-20 User Manual

Page 90

background image

12  Parameters

SMA Solar Technology AG

90

SCxxxHE-20-BE-BEN111210

Operating Manual

P-W

Limits the active
power in kW
The maximum
active power is
"Pmax".

0 kW …

1 000 kW

SC 500HE-20

550 kW

0 kW …

1 000 kW

SC 630HE-20

700 kW

0 kW …

1 000 kW

SC 720HE-20

792 kW

0 kW …

1 000 kW

SC 760HE-20

836 kW

0 kW …

1 000 kW

SC 800HE-20

880 kW

P-WNom

Limits the active
power in %

0% … 100%

100%

WCtlHzMod

**

Frequency
regulation setpoint

Off

Deactivated

country-

specific

On

Activated

P-HzStr

**

Start of frequency
regulation

40 Hz … 70 Hz

country-

specific

P-HzStop

**

End of frequency
regulation

40 Hz … 70 Hz

country-

specific

P-WGra

**

Gradient of power
reduction

1%/Hz …

100%/Hz

40%/Hz

Qlimit

*

Reactive power of
device

245 kVAr

SC 500HE-20

310 kVAr

SC 630HE-20

346 kVAr

SC 720HE-20

365 kVAr

SC 760HE-20

385 kVAr

SC 800HE-20

Qmax

**

Limitation of
Sunny Central's
reactive power

0 kVAr …

245 kVAr

SC 500HE-20

245 kVAr

0 kVAr …

310 kVAr

SC 630HE-20

310 kVAr

0 kVAr …

346 kVAr

SC 720HE-20

346 kVAr

0 kVAr …

365 kVAr

SC 760HE-20

365 kVAr

0 kVAr …

385 kVAr

SC 800HE-20

385 kVAr

PFAbsMin

*

Limitation of the
displacement
power factor cos φ

0.9

Name

Description

Value/Range

Explanation

Default

value

This manual is related to the following products: