SMA SC 500HE-20 User Manual
Page 90
12 Parameters
SMA Solar Technology AG
90
SCxxxHE-20-BE-BEN111210
Operating Manual
P-W
Limits the active
power in kW
The maximum
active power is
"Pmax".
0 kW …
1 000 kW
SC 500HE-20
550 kW
0 kW …
1 000 kW
SC 630HE-20
700 kW
0 kW …
1 000 kW
SC 720HE-20
792 kW
0 kW …
1 000 kW
SC 760HE-20
836 kW
0 kW …
1 000 kW
SC 800HE-20
880 kW
P-WNom
Limits the active
power in %
0% … 100%
100%
WCtlHzMod
Frequency
regulation setpoint
Off
Deactivated
country-
specific
On
Activated
P-HzStr
Start of frequency
regulation
40 Hz … 70 Hz
country-
specific
P-HzStop
End of frequency
regulation
40 Hz … 70 Hz
country-
specific
P-WGra
Gradient of power
reduction
1%/Hz …
100%/Hz
40%/Hz
Qlimit
Reactive power of
device
245 kVAr
SC 500HE-20
310 kVAr
SC 630HE-20
346 kVAr
SC 720HE-20
365 kVAr
SC 760HE-20
385 kVAr
SC 800HE-20
Qmax
Limitation of
Sunny Central's
reactive power
0 kVAr …
245 kVAr
SC 500HE-20
245 kVAr
0 kVAr …
310 kVAr
SC 630HE-20
310 kVAr
0 kVAr …
346 kVAr
SC 720HE-20
346 kVAr
0 kVAr …
365 kVAr
SC 760HE-20
365 kVAr
0 kVAr …
385 kVAr
SC 800HE-20
385 kVAr
Limitation of the
displacement
power factor cos φ
0.9
Name
Description
Value/Range
Explanation
Default
value