12.3 Sunny String-Monitor

Name

Description

Value/Range

Explanation

Default

value

TMittelung

*

Duration for averaging
the measured current
value

0 s … 6 000 s

30 s

String Anzahl

*

Number of detected PV
strings

0 … 8

0

SSM Identifier

*

Identification number of
the Sunny String-
Monitors

1 … 99

0

Group String 1

*

Assigns the PV strings to
the respective group
Parameter exists for all
8 measuring channels

0 … 3

0

Group String

*

All groups

0 … 3

0

No.of String 1

*

Number of connected
strings per measuring
channel
Parameter exists for all
8 measuring channels
Call the SMA Service
Line if you would like to
use this function

1 … 4

1

No.of Strings

*

All groups

1 … 4

1

Monitoring1 On* Starts monitoring of PV

strings in group 1
Parameter exists for all
8 measuring channels

0:00 a.m. …

11:59 p.m

0

Monitoring1 Off

*

Monitoring of PV strings
in group 1 ends
Parameter exists for all
8 measuring channels

0:00 a.m. …

11:59 p.m

0

Monitoring On

*

PV string monitoring of
all measuring channels
begins

0:00 a.m. …

11:59 p.m

0

Monitoring Off

*

PV string monitoring of
all measuring channels
stops

0:00 a.m. …

11:59 p.m

0