2 sunny central string-monitor controller, Sunny central string-monitor controller, H-on – SMA SC 500HE-20 User Manual
Page 100: Cab1, Cab2

12 Parameters
SMA Solar Technology AG
100
SCxxxHE-20-BE-BEN111210
Operating Manual
12.2 Sunny Central String-Monitor Controller
ExlStrStpEna
Enable external
shutdown signal/
remote shutdown
Off
Deactivated
Off
On
Activated
ExlTrfErrEna
Enable hermetic
protection of medium
voltage transformer
Off
Deactivated
On
On
Activated
*
These parameters are only visible after the installer password has been entered.
**
These parameters can only be changed after the installer password has been entered.
Name
Description
Value/Range
Explanation
Default
value
TolGr1
*
Currents from group
1 deviate from mean
value
Parameter exists for
all 6 groups
5% … 100%
13%
MoniTmGr1On
Time when group 1
monitoring begins
Parameter exists for
all 8 groups
7:00 a.m. …
7:00 p.m.
10:00 a.m.
MoniTmGr1Off
Time when group 1
monitoring stops
Parameter exists for
all 6 groups
7:00 a.m. …
7:00 p.m.
3:00 p.m.
MoniTmGrAllOn
Time when monitoring
of all groups begins
7:00 a.m. …
7:00 p.m.
10:00 a.m.
MoniTmGrAllOff
Time when monitoring
of all groups stops
7:00 a.m. …
7:00 p.m.
3:00 p.m.
Ackn
Acknowledge error in
Sunny Central String-
Monitor Controller
---
---
Ackn
Select parameter to
acknowledge an
error
Name
Description
Value/Range
Explanation
Default
value