beautypg.com

11 "varctlvol" procedure, Varctlvol" procedure – SMA SC 500HE-20 User Manual

Page 52

background image

6  Setpoint for Active Power and Reactive Power

SMA Solar Technology AG

52

SCxxxHE-20-BE-BEN111210

Operating Manual

6.2.11 "VArCtlVol" Procedure

Reactive power is set depending on the grid voltage. The reactive power target value is adjusted in
stages.

Figure 17: Curve for reducing reactive power depending on grid voltage

If the grid voltage and the parameterizable voltage difference "Q-VDif" change for the configurable
duration of "Q-VDifTm", the reactive power setpoint is adapted to the "Q-VArGra" value.
The parameterization of this function depends on the medium voltage.

Contact the SMA Service Line before changing any parameters

Contact the SMA Service Line before selecting or configuring the "VArCtlVol" procedure.

Used parameters

Q-VDif
Q-VArGra
Q-VDifTm
Q-VRtgOfsNom

This manual is related to the following products: