6  Setpoint for Active Power and Reactive Power

SMA Solar Technology AG

56

SCxxxHE-20-BE-BEN111210

Operating Manual

6.2.13 Displaying Error Messages and Warnings for the Reactive

Power Setpoint

The "Q-VArModFailStt" channel shows the error messages or warnings associated with the reactive
power setpoint

Displaying the "Q-VArModFailStt" channel

• Display the spot value of the "Q-VArModFailStt" channel on the SC-COM interface

(see section 5.1 "Displaying Spot Values", page 34).

Display

Description

Measure

Off

No procedure for specifying the reactive
power setpoint has been chosen.

None

Ok

A procedure for specifying the reactive
power setpoint has been chosen and
there are no errors.

None

ComFail

The "VArCtlCom" or "PFCtlCom"
procedure has been chosen and the
expected signal with a valid reactive
power setpoint has been absent for at
least 5 minutes.

• Check if SC-COM is working.
• Make sure the SC-COM can be

accessed externally and is
displaying the data of the inverter.

• Check if the cables between the

SC-COM and the inverters are
OK.

• Check if the cables inside the

SC-COM are OK.

AnInFail

The "VArCnstNomAnIn" or
"PFCnstNomAnIn" procedure has been
chosen and the value measured at the
analog input is less than 2 mA.

• Check the analog input.