beautypg.com

5 error 34xx … 40xx ‒ pv array errors, Error 34xx … 40xx ‒ pv array errors – SMA SC 500HE-20 User Manual

Page 76

background image

10  Troubleshooting

SMA Solar Technology AG

76

SCxxxHE-20-BE-BEN111210

Operating Manual

10.5 Error 34xx … 40xx ‒ PV Array Errors

1301

Error message
< Left Phase sequence >
Measure
< Check grid connection and phase sequence >

– Check phase position.
– Make sure all fuses are switched on.

Error no.

Error message, cause of error and corrective measure

34xx

Cause of error
An overvoltage is present.
Error message 3403
< DC-Overvoltage >

– The voltage of the PV array is too high.

Error message 3404
< DC overvoltage peak >

– A direct overvoltage peak has occurred in the PV array.

Measure
< Check DC generator >

– Check DC input voltage.

Check module wiring and plant design.

Error no.

Cause of error, error message and corrective measure