SMA SC 500HE-20 User Manual
Page 94

12 Parameters
SMA Solar Technology AG
94
SCxxxHE-20-BE-BEN111210
Operating Manual
Q-VDifTm
Time span in which
the voltage change
must wait before the
reactive power
setpoint "Q-VArGra"
changes
0 s … 120 s
1 s
Q-VRtgOfsNom
Changes the rated
voltage "VRtg" of
the voltage-
dependent reactive
power controller
Parameter is active
only if parameter
"Q-VArMod" is set
to "VArCtlCol"
− 10% … +10%
0%
Q-VArGraNom
Reactive power
gradient
0%/V … 10%/V
0%/V
Q-VolWidNom
Voltage width
0% … 20%
0%
Q-VolNomP1
Voltage on point 1
0% … 20%
0%
Q-VolNomP2
Voltage on point 2
0% … 20%
0%
Q-VArTmsSpnt
Time setting of the
characteristic curve
point
1 s … 60 s
10 s
Q-VArTmsVtg
Delay of grid
voltage
1 s … 60 s
10 s
Q-EnaTmsVtg
Connection delay
of grid voltage
Off
Off
On
Gradient of active
power change
1% … 20%
20%
WGraEna
Activation of the
active power
change gradients
Off
Deactivated
Off
On
Activated
WGraReconEna
Activation of the
active power
increase ramp for
reconnection
Off
Deactivated
country-
specific
On
Activated
Name
Description
Value/Range
Explanation
Default
value