12 Parameters
SMA Solar Technology AG
96
SCxxxHE-20-BE-BEN111210
Operating Manual
Activation time for
undervoltage level 2
0 ms …
1 000 000 ms
country-
specific
VCtlMin
Threshold value for
undervoltage
activation level 3
0% … 100%
country-
specific
VCtlMinTm
Activation time for
undervoltage level 3
0 ms …
1 000 000 ms
country-
specific
Threshold value for
overvoltage
100% … 150%
country-
specific
VCtlPeakMaxTm
Activation time for
overvoltage
0 ms … 20 ms
country-
specific
VCtlOpMinNom
Minimal connection
voltage
0% … 100%
country-
specific
VCtlOpMaxNom
Maximum connection
voltage
100% … 200%
country-
specific
HzCtlOpMin
Minimum connection
frequency
country-specific
country-
specific
HzCtlOpMax
Maximum connection
frequency
country-specific
country-
specific
HzCtlMax
Threshold value for
overfrequency level 3
country-specific
country-
specific
HzCtlMaxTm
Activation time for
overfrequency level 3
0 ms …
1 000 000 ms
country-
specific
threshold value for
overfrequency level 2
country-specific
country-
specific
Activation time for
overfrequency level 2
0 ms …
1 000 000 ms
100 ms
HzCtlhLim
Threshold value for
overfrequency level 1
country-specific
country-
specific
HcCtlhLimTm
Activation time for
overfrequency level 1
0 ms …
1 000 000 ms
100 ms
HzCtllLim
Threshold value for
underfrequency
level 1
country-specific
country-
specific
HzCtllLimTm
Tripping time for
underfrequency
level 1
0 ms …
1 000 000 ms
100 ms
Name
Description
Range
Explanation
Default
value