6  Setpoint for Active Power and Reactive Power

Operating Manual

SCxxxHE-20-BE-BEN111210

43

6.1.7 "WCnstNomAnln" Procedure

Active power limitation is set at the input terminals using an analog signal for specifying the setpoint
(see enclosed installation manual). This is usually accomplished by using a radio ripple control
receiver.
The current of the connected signal determines the rated active power.
The analog measured values must be between 4 mA … 19 mA. If the analog signal is smaller than
2 mA, the error message will be displayed in the "P-WModFailStt" spot value.

The analog value is converted to a target value for power limitation. Here, the "Pmax" parameter is
the end point of the linear characteristic curve.

6.1.8 Displaying Error Messages and Warnings for Active Power

Limitation

The "P-WModFailStt" spot value displays the error messages or warnings associated with active
power limitation.

Displaying the "P-WModFailStt" Channel

• Display the "P-WModFailStt" spot value on the SC-COM interface (see section 5.1 "Displaying

Spot Values", page 34).

Signal

Power limit

Description

< 2 mA

Last valid value or "Pmax" after
restart

Signal is in the invalid range.

2 mA … 4 mA

0 kW

No power is fed into the grid.

4 mA … 19 mA

0 kW … Pmax

Fed-in energy is determined
using a characteristic curve

> 19 mA

Pmax

Fed-in energy equals Pmax.

Used parameters

None

Display

Description

Measure

Off

No procedure for limiting active power
has been chosen.

None

Ok

A procedure for limiting active power
has been chosen and there are no
errors.

None