SMA SC 500HE-20 User Manual
Page 55
SMA Solar Technology AG
6 Setpoint for Active Power and Reactive Power
Operating Manual
SCxxxHE-20-BE-BEN111210
55
Figure 21: Curve for reducing reactive power with deadband and hysteresis
The "Q-VArTmsSpnt" parameter determines the delay time after which the calculated reactive power
setpoint is actively used.
In order to prevent several systems with this function from influencing each other, the "Q-VArTmsVtg"
parameter can be used to set a delay time. This delay time indicates for how long a voltage change
must be pending before a change in reactive power output will result. This allows several systems to
alternately regulate the grid voltage at the grid connection joint.
The "Q-EnaTmsVtg" parameter can be used to switch the delay time on and off.
Used parameters
Q-VolWidNom
Q-VolNomP1
Q-VolNomP2
Q-VArGraNom
Q-VArTmsSpnt
Q-VArTmsVtg
Q-EnaTmsVtg