beautypg.com

4 error 01xx … 13xx ‒ grid errors, Error 01xx … 13xx ‒ grid errors – SMA SC 500HE-20 User Manual

Page 74

background image

10  Troubleshooting

SMA Solar Technology AG

74

SCxxxHE-20-BE-BEN111210

Operating Manual

10.4 Error 01xx … 13xx ‒ Grid Errors

Error no.

Cause of error, error message and corrective measure

01xx
02xx

Cause of error
Grid voltage is outside the permissible range or a phase of the power distribution
grid has failed.
Error message 0103
< Grid overvoltage slow >

– Grid voltage is too high. Overvoltage from redundant monitoring

detected.

Error message 0104
< Grid overvoltage fast >

– Grid voltage is too high. Overvoltage from standard monitoring detected.

Error message 0203
< Grid undervoltage slow >

– Grid voltage is too low. Undervoltage from redundant monitoring

detected.

Error message 0204
< Grid undervoltage fast >

– Grid voltage is too low. Undervoltage from standard monitoring detected.

Error message 0205
< Grid failure >

– A power distribution grid phase has failed.

Measure
< Check grid voltage >

– Check the grid voltage.
– Check grid connections.
– See if the power distribution grid is stable.
– Make sure the external fuses are working properly.
– Make sure the AC cable is connected securely.