12  Parameters

Operating Manual

SCxxxHE-20-BE-BEN111210

91

Q-VArMod

**

Procedure selection
for the reactive
power setpoint

Off

Sets reactive power to
0 kVAr and
displacement power
factor cos φ to 1

Off

VArCtlCom

Sets reactive power via
Power Reducer Box

PFCtlCom

Specifies the
displacement power
factor cos φ and the
excitation of the
displacement power
factor via the Power
Reducer Box

VArCnst

Specifies the reactive
power in kVAr via the
parameter "Q-VAr"

VArCnstNom

Specifies the reactive
power in % via the
parameter "Q-VArNom"

VArCnstNomAnIn Sets the reactive power

using the control unit on
the analog input
"ExtSolQ"

PFCnst

Manual specification of
the displacement power
factor cos φ and the
excitation of the
displacement power
factor via parameters
"PF-PF" and "PF-PFExt"

PFCnstAnIn

Sets the displacement
power factor cos φ on
the analog input
"QExlSpnt" via the
control unit

PFCtlW

Sets the displacement
power factor cos φ
depending on the feed-in
power

Name

Description

Value/Range

Explanation

Default

value