12 Parameters
Operating Manual
SCxxxHE-20-BE-BEN111210
101
ErrLevGr1
Sensitivity of error
detection for group 1
Parameter exists for
all six groups
24 sensitive
50 min ‒ 10%
32 regular
24 regular
50 min ‒ 14%
24 insensitive
50 min ‒ 18%
32 sensitive
35 min ‒ 10%
32 regular
35 min ‒ 13%
32 insensitive
35 min ‒ 16%
64 sensitive
15 min ‒ 7%
64 regular
15 min ‒ 9%
64 insensitive
15 min ‒ 10%
ComBaud
Baudrate
1 200 Baud
19 200
Baud
**
4 800 Baud
9 600 Baud
19 200 Baud
38 400 Baud
57 600 Baud
DevFunc
Manages the Sunny
String-Monitors
AutoDetect_
SSMU
Searches for and
deletes Sunny String-
Monitors that have
already been
detected
0
DetectSSMU
Retry
Only searches for
undetected Sunny
String-Monitors
DelAll_SSMU
Deletes all detected
Sunny String-
Monitors
Factory
Resets all parameters
to their default
settings
*
These parameters are only visible after the installer password has been entered.
**
If the PV plant is equipped with a Sunny String-Monitor Controller, the baud rate of all components must be set to
19 200 baud.
Name
Description
Value/Range
Explanation
Default
value