Analog Current Input

Maximum error in temperature range*

±2.0%

Terminal

Spring-cage terminal with actuation lever on the

electronic assembly

Maximum cable length

30 m

Conductor cross-section

0.08 mm

2

 to 1.00 mm

2

Cable gland

Multiple feed-through

Sealing range of cable gland

3.2 mm to 6.5 mm / 5.0 mm to 10.2 mm

* based on the measuring range end value

Digital Output

Type

Potential-free change-over contact

Maximum switching power AC

250 V

AC

/ 2 A

Maximum switching power DC

24 V

DC

/ 2 A

48 V

DC

/ 1 A

Minimum electrical endurance when the maxi-
mum switching voltage and maximum switching
current are complied with

1,000,000 switching cycles

Terminal

Spring-cage terminal with actuation lever on the

electronic assembly

Conductor cross-section

0.5 mm

2

to 6.0 mm

2

Cable gland

Multiple feed-through

Sealing range of cable gland

3.2 mm to 6.5 mm / 5.0 mm to 10.2 mm

Data Transmission Copper Wire

Data interface

Modbus (TCP)

Local area network (LAN)

Ethernet

Connection without surge arrester

LSA+

Connection with surge arrester*

RJ45

Recommended cable type

Cat5 cable with shielding S-UTP, F-UTP or higher

Maximum cable length

100 m

Cable gland

Multiple feed-through

Sealing range of cable gland

3.2 mm to 6.5 mm / 5.0 mm to 10.2 mm

* available as an accessory (see Section 14, page 72)