SMA SSM-U-1615 User Manual
Page 70

Analog Current Input
Maximum error in temperature range*
±2.0%
Terminal
Spring-cage terminal with actuation lever on the
electronic assembly
Maximum cable length
30 m
Conductor cross-section
0.08 mm
2
to 1.00 mm
2
Cable gland
Multiple feed-through
Sealing range of cable gland
3.2 mm to 6.5 mm / 5.0 mm to 10.2 mm
* based on the measuring range end value
Digital Output
Type
Potential-free change-over contact
Maximum switching power AC
250 V
AC
/ 2 A
Maximum switching power DC
24 V
DC
/ 2 A
48 V
DC
/ 1 A
Minimum electrical endurance when the maxi-
mum switching voltage and maximum switching
current are complied with
1,000,000 switching cycles
Terminal
Spring-cage terminal with actuation lever on the
electronic assembly
Conductor cross-section
0.5 mm
2
to 6.0 mm
2
Cable gland
Multiple feed-through
Sealing range of cable gland
3.2 mm to 6.5 mm / 5.0 mm to 10.2 mm
Data Transmission Copper Wire
Data interface
Modbus (TCP)
Local area network (LAN)
Ethernet
Connection without surge arrester
LSA+
Connection with surge arrester*
RJ45
Recommended cable type
Cat5 cable with shielding S-UTP, F-UTP or higher
Maximum cable length
100 m
Cable gland
Multiple feed-through
Sealing range of cable gland
3.2 mm to 6.5 mm / 5.0 mm to 10.2 mm
* available as an accessory (see Section 14, page 72)
13 Technical Data
SMA Solar Technology AG
Operating Manual
SSMUXX15-BE-en-10
70