3 maintenance work, 1 checking the dc load-break switch – SMA SSM-U-1615 User Manual
Page 54
Maintenance under voltage-free conditions
Task
See
Checking the protective covers
Performing the visual inspection
Checking the condensate drain
Checking the vent plug
Checking the seals
Checking the labels
Checking the LEDs
Checking the bolted, clamp and plug connections
Checking the inline fuse connectors*
Installation manual of the inline fuse con-
nector
Checking the ground connection
* available as an accessory
10.3 Maintenance Work
10.3.1 Checking the DC Load-Break Switch
1. Disconnect the DC subdistribution from voltage sources (see Section 8.2, page 47)
2. Check whether the DC load-break switch has disconnected the contacts as follows:
• If you are using the alarm contact set (see Section 14, page 72), check on the user
interface of the inverter whether the switching state of the DC load-break switch is
displayed correctly.
• If no alarm contact set is in use, check in the
inspection window of the DC load-break
switch whether the switch is open.
or
Use a continuity tester to perform a
continuity check.